Product overview
2.1 Properties
Interface module IM 155-6 PN/2 HF (6ES7155-6AU01-0CN0)
Manual, 10/2018, A5E03915895-AH
15
The server module has the following properties:
●
Terminates the backplane bus of the ET 200SP distributed I/O system
●
Includes a holder for 3 spare fuses (5 × 20 mm).
●
Provides station functions, e.g., group diagnostics: No supply voltage L+, status bytes.
●
Identification data I&M 0 to 4
Note
You need to configure and assign parameters to the server module in the configuration
software.
Place the server module in the last slot of the configuration. If there are 64 I/O modules, the
server module is plugged in slot 65.
You can find more information in the Server module
http://support.automation.siemens.com/WW/view/en/63257531
) manual.
First BaseUnit of an ET 200SP in the configuration
The interface modules support plugging a dark-colored BaseUnit in slot 1. This means that
modules without a connection to the integrated voltage buses P1 and P2 can now also be
configured starting with slot 1. Currently, this applies to the following modules:
●
AI Energy Meter ST
●
DI 4 x 120…230 V AC ST (6ES7131-6FD00-0BB1)
●
DQ 4 x 24…230 V AC/2 A ST (6ES7132-6FD00-0BB1)
Note
First BaseUnit of an ET 200SP in the configuration
Please note the information on limiting the overvoltage and power rating in the AC I/O
module manuals.
You route the infeed of the 24 V DC supply voltage over an external fuse.
The 24 V DC supply voltage is provided by a light-colored BaseUnit.
Requirement for configuration of these modules in slot 1:
●
Configuration via GSD or GSDML
●
Configuration as of STEP 7 V5.5 SP4 with
–
HSP0255 V3.0 for IM155-6 PN HF
●
Configuration as of STEP 7 V13 SP1
See also