Interrupts, error messages, diagnostics and system alarms
5.2 Interrupts
Interface module IM 155-6 PN/2 HF (6ES7155-6AU01-0CN0)
38
Manual, 10/2018, A5E03915895-AH
Error display
Table 5- 4
Error display
Error type
(MAINT)
Error location
(ERROR/ MAINT)
Cause of error
Solution
1
65
•
No server module
•
Interruptions on the backplane bus
•
Short circuit of communication on
the backplane bus
Check the configuration
of the ET 200SP.
Note
A short circuit in the backplane bus supply or the bus connection supply is indicated by the
following LEDs:
•
PWR LED: On
•
RN, ER and MT LED: Off
5.2
Interrupts
Introduction
The I/O device triggers interrupts as a reaction to specific errors. Interrupts are evaluated
based on the I/O controller used.
Evaluating interrupts with I/O controllers
The ET 200SP distributed I/O system supports the following interrupts:
●
Diagnostic error interrupts
●
Hardware interrupts
●
Pull/plug interrupts
●
Maintenance events
In the event of an interrupt, interrupt OBs are automatically called in the CPU of the IO
controller.
Information on the cause and class of the error is already available, based on the OB
number and start information.
Detailed information on the error event can be obtained in the error OB using the instruction
"RALRM" (read additional interrupt information).