Basic Principles of Serial Data Transmission
2-14
Point-to-point connection CP 440 Installation and Parameter Assignment
A5E00057742-02
Code Transparency
The code transparency of the procedure depends on the selection of the
parameterized end criterion and the flow control:
•
With one or two end-of-text characters
– Not code-transparent
•
When the end criterion is the character delay time or a fixed message frame
length
– Code-transparent
•
Code-transparent operation is not possible when XON/XOFF flow control is
used.
Code-transparent means that any character combination can occur in the user
data without the end criterion being detected.