Parameter
Value range
Default
Parameter re‐
assignment in
RUN
Efficiency range
(Page 21)
• None
• 0.05 ms
• 0.1 ms
• 0.4 ms
• 0.8 ms
• 1.6 ms
• 3.2 ms
• 12.8 ms
• 20 ms
3.2 ms
Yes
Channel
Hardware interrupts positive
edge
• Activated
• Deactivated
Deactivated
Yes
Channel
Hardware interrupts nega‐
tive edge
• Activated
• Deactivated
Deactivated
Yes
Channel
Potential group (Page 22)
• Use potential group of the left
module
• Allow new potential group
Use potential group
of the left module
No
Module
1
The wire break diagnostics can only be enabled when the "Check for wire break" parameter is enabled.
2
If you use simple encoder contacts, you need to connect a resistor in parallel to enable a wire break check to be performed
when the contacts are open. The resistor used depends on the nominal input voltage of the module.
3
When time stamping with an accuracy of 1 ms is enabled, the input delay on all channels is switched off and the pulse
stretching and hardware interrupt for positive/negative edge is disabled on all channels (not adjustable).
6.3
Parameter reassignment
Definition
Each configuration change resets the corresponding reaction. Changing the configuration of a
function does not affect other functions.
6.4
Explanation of the module/channel parameters
6.4.1
Channel activated
Definition
Specifies whether a channel is activated or deactivated.
Parameters
6.4 Explanation of the module/channel parameters
DI 8x24...125VDC HA
20
Equipment Manual, 10/2021, A5E39288633-AD