Mobile Panel 277 IWLAN, Mobile Panel 277F IWLAN
12
A5E02615843-01, 08/2009
Safety notes for Mobile Panel 277F IWLAN
WARNING
Note the function manual "Fail-safe operation of the Mobile Panel 277F IWLAN"
Please pay attention to the function manual "Fail-safe operation of the Mobile Panel 277F IWLAN" as well as the warnings
and additional information available in the Internet at:
Complete documentation on the Mobile Panel 277 IWLAN and Mobile Panel 277F IWLAN
http://support.automation.siemens.com/WW/view/en/26268960
)
The function manual "Fail-safe operation of the Mobile Panel 277F IWLAN" is available in German, English and Japanese.
Automatic transfer
WARNING
Do not use automatic transfer
The automatic transfer (Control Panel, option "Remote Control") for the HMI device must not be used.
Use the manual transfer.
Power management
NOTICE
Screen contents not updated reliably
The screen contents of the HMI device are not updated reliably in the following situation.
●
You use the "Hardware Support Package (HSP) Mobile Panel 277 IWLAN and Mobile Panel 277F IWLAN for WinCC
flexible 2007" (V1.1) software.
●
The HMI device is logged onto the effective range.
●
The following settings are active for the power management:
–
A time period has been set for the "Switch off screen" option.
–
The "Reduce brightness" option has been disabled with the entry "never".
You have the following options to prevent this type of behavior:
●
Option 1: Install WinCC flexible 2008 SP1.
●
Option 2: Configure a time period for the "Reduce brightness" option.
Summary of Contents for SIMATIC 277 IWLAN
Page 4: ......
Page 6: ...2 1 Welcome ...
Page 9: ...5 HMI Device Mobile Panel 277 IWLAN Getting Started 04 2008 A5E01004533 01 ...
Page 10: ...6 2 Configuring the WLAN ...
Page 42: ...38 3 Creating the Project ...
Page 56: ...52 4 Planning a Wireless Network ...
Page 61: ...57 HMI Device Mobile Panel 277 IWLAN Getting Started 04 2008 A5E01004533 01 ...