3WL air circuit breakers
3.5 External CubicleBUS modules
3WL/3VL circuit breakers with communication capability - PROFIBUS
58
System Manual, 03/2011, A5E01051353-02
3.5
External CubicleBUS modules
3.5.1
General information
General (description and equipment)
External CubicleBUS modules enable communication of the SENTRON WL circuit breaker
with secondary devices in the circuit breaker field. It can be used, for example, to control
analog indicators, to transfer alarms and the reason for tripping the circuit breaker, and to
read in additional control signals. With the help of one of these modules, a Zone Selective
Interlocking can also be implemented for short circuits.
Five different CubicleBUS modules can output data from the CubicleBUS system.
All external CubicleBUS modules have the same housing. The CubicleBUS can be
connected to X1 and X2 with an RJ45 connector, or it can be connected to X3. This depends
on whether or not a COM15 is available.
①
LED
②
Rotary coding switch
③
X1: CubicleBUS
④
X2: CubicleBUS
⑤
X3: CubicleBUS
⑥
X5: Inputs/outputs
⑦
X4: Inputs/outputs
⑧
Push to trip button
Figure 3-13 External CubicleBUS module