Data library
8.6 Data sets
3WL/3VL circuit breakers with communication capability - PROFIBUS
208
System Manual, 03/2011, A5E01051353-02
8.6.7
Data set DS 69 status of the modules
The table below shows the content of data set 69 in which the statuses of the inputs on the
digital input modules and the input on the COM15 module are transmitted. It also contains
the switch positions on the digital input modules and output modules on the CubicleBUS.
The table below contains the data sets DS69: Status of the modules (length 43 bytes, read-
only):
Table 8- 20 Content of data set 69
Byte
Description
Data
point
Source
WL
Source VL Format Length
(bits)
Scaling
0
Status of the inputs of the digital input module
1
110
DI1
—
Hex
8
—
1
Status of the inputs of the digital input module
2
114
DI2
—
Hex
8
—
2
Controls the outputs of the communication
module (e.g. switching the breaker) and
checkback signals
19
COM15
COM20
Format
(19)
8
—
3
Switch position at the digital input module 1
111
DI1
—
Format
(111)
8
—
4
Switch position at the digital input module 2
115
DI2
—
Format
(111)
8
—
5
Switch position at the digital output module 1
119
DO1
—
Format
(119)
8
—
6
Switch position at the digital output module 2
124
DO2
—
Format
(119)
8
—
7
Reserved
—
—
—
—
32
—
11
PROFIBUS write protection (DPWriteEnable)
14
COM15
COM20
Format
(14)
1
—
12
Reserved
—
—
—
—
8
—
13
6 PROFIBUS bits for the digital configurable
output module
426
COM15
—
Format
(426)
6
—
14
Reserved
—
—
—
—
120
—
29
Property byte for byte 13 (6 PROFIBUS bits
for the digital configurable output module)
—
COM15
—
PB
8
—
30
Property byte for byte 0 (status of the inputs of
digital input module 1)
—
DI1
—
PB
8
—
31
Property byte for byte 1 (status of the inputs of
digital input module 2)
—
DI2
—
PB
8
—
32
Property byte for byte 2 (controls the outputs
of the communication module (e.g. switching
the breaker) and checkback signals)
—
COM15
COM20
PB
8
—
33
Property byte for byte 3 (switch position on the
digital input module 1)
—
DI1
—
PB
8
—
34
Property byte for byte 4 (switch position on the
digital input module 2)
—
DI2
—
PB
8
—
35
Property byte for byte 5 (switch position on
digital output module 1)
—
DO1
—
PB
8
—