Installation Instructions

RESIDUAL SETTING (OUTGOING CIRCUIT
METHOD)– This is the standard position to which
the breaker is set when shipped from the factory.
With the switch in this position the circuit breaker
may be used on 3 phase 3 wire or, with the addition
of an external neutral sensing transformer, on 3
phase 4 wire systems.  See Neutral Sensing Trans-
former section for more information.

GROUND RETURN SETTING (GROUND RETURN
METHOD) – This setting may only be used for ser-
vice disconnects or separately derived systems.
With the switch in this position, the circuit breaker
may be used on 3 phase 3 wire and 3 phase 4 wire
systems.  An external sensing transformer, which is
installed on the main bonding jumper, is required
for this method.  See Neutral Sensing Transformer
section for more information.

Neutral Sensing Transformer

An external transformer is required for circuit break-
ers equipped with ground fault protection when op-
erating in the RESIDUAL mode on 3 phase 4 wire
systems and when operating in the GROUND RE-
TURN mode on any system.  The sensors listed
below must be used for these applications.  The sen-
sor catalog number must be matched to the circuit
breaker Maximum Continuous Current rating (ln) as
shown in the table.  Please  note that sensors used
with other breaker types cannot be used with the
SJD/SLD circuit breakers.  Installation instructions
are included with the sensors.

Transformer

Circuit

Transformer

Catalog No.

Breaker Rating

__Color__

N02SJD

200 Amps

GREEN

N03SJD

300 Amps

GREEN

N04SJD

400 Amps

GREEN

N05SLD

500 Amps

GREEN

N06SLD

600 Amps

GREEN

Electronic Testing

Sensitrip III solid state molded case circuit break-
ers may be tested for electronic functionality by the
use of a TS-31 test set available from local  Siemens
sales offices.

NOTE:  Time current characteristic curves and in-
formation on factory installed accessories can be
obtained from local Siemens sales offices.

Maintenance

JD and LD frame circuit breakers are designed to
provide years of maintenance free service.  Experi-
ence has shown that properly applied molded case
circuit breakers normally do not require mainte-
nance.  However, some industrial users may choose
to establish an inspection and maintenance proce-
dure to be carried out on a regular basis.  For de-
tailed information, consult applicable NEMA publi-
cation or your local Siemens sales office.

NOTE:  Do not spray or allow any petroleum based
chemicals, solvents or paints to contact the molded
parts or nameplates.

This product is covered by one or more of the following patents:  4,631,525;  4,513,267;  4,484,164.

Summary of Contents for Sensitrip III Sentron Series

Page 1: ...e installation procedure consists of inspecting attaching required accessories mounting the cir cuit breaker and connecting and torquing the line and load wire connectors Mounting hardware and unmounted wire connec tors where required are available as separate cata log items A Turn off and lock out all power before installing or servicing this circuit breaker B Make sure that the device is suitabl...

Page 2: ...ory terminals should be connected 7 After the circuit breaker is installed check all mounting hardware for secureness Check wire connectors for correct torque require ments Torque values for line and load con nectors are provided on the circuit breaker nameplate Fig 3 Fig 2 9 75 4 40 6 86 OF HANDLE ESCUTCHEON OF HANDLE ESCUTCHEON DRILL ANDTAP 1 4 20 HOLE 4 OR 6 PLS REQUIRED FOR SCJD6 SCLD6 ONL Y O...

Page 3: ...tches that must be properly set to mechanical detent click stop positions An improper switch setting will cause the trip unit to default as a fail safe condition to the lowest permissive setting and consequently may result in unintentional or nuisance tripping Continuous Current lr and LongTime Delay All models have a Continuous Current and Long Time Delay adjustment This single knob adjusts the C...

Page 4: ...ent to set the Ground Fault Pickup current lg as a percentage of the Maximum Continuous Cur rent rating ln The pickup has a built in time delay Three time delays are available of 0 1 0 2 or 0 4 seconds These are selected by using the appro priate area of the setting Below 50 Maximum Continuous Current rating ln the pickup delay has an I2 t slope See Figure 8 The ground fault option has two modes o...

Page 5: ...n operating in the GROUND RE TURN mode on any system The sensors listed below must be used for these applications The sen sor catalog number must be matched to the circuit breaker Maximum Continuous Current rating ln as shown in the table Please note that sensors used with other breaker types cannot be used with the SJD SLD circuit breakers Installation instructions are included with the sensors T...

Reviews: