Operating modes
5.1 Low-fire operation
Low-fire operation means that only small amounts of heat are drawn from the boiler.
Using relay K1
Burner release
, the 2-position controller ensures control to the setpoint
by switching the burner on and off like a thermostat.
This mode of control is known as the thermostat
function. An adjustable switching
differential ensures that the burner’s switching frequency can be selected, aimed at
reducing wear.
ON
OFF
7866d03e/1011
Figure 6: Control sequence of heating controller
Modulating and 2-stage operation:
Actual value lies between switch-on
threshold
HYS1
and switch-off threshold
HYS3
.
If the controller is set to cooling mode, temperature limits
HYS4
and
HYS6
apply. In that
case, relay K1
Burner release
is used for controlling the cooling equipment.
7866d04e/1011
ON
OFF
Figure 7: Control sequence of cooling controller
Modulating and 2-stage operation:
Actual value lies between switch-on
threshold
HYS4
and switch-off threshold
HYS6
.
Thermostat function
Heating controller
Cooling controller