With plant types x–4, this function is required to detect bottlenecks in the heat supply
from the district heat network. Undertemperature supervision triggers an error message
when, for a defined period of time during a demand for heat, the flow temperature falls
below the flow temperature setpoint by more than 10 K. This period of time can be set
on operating line 143. The flow alarm becomes inactive as soon as the limit is ex-
ceeded again.
Flow alarm for undertemperature supervision:
t
T
V
w
x
23
83D
07
t
A
t
1
t
2
ERROR
t Time
T
V
Flow
temperature
t
1
Start of ERROR display
w
Setpoint
t
2
End of ERROR display
x
Actual value
t
A
Waiting time (set on operating line 143)
"Forbidden” range
The flow alarm appears on the display as ERROR and, on operating line 50, with error
code 123.
The flow alarm can be deactivated by entering --:-- .
22.5 Winter- / summertime changeover
The change from wintertime to summertime, and vice versa, is made automatically. If
international regulations change, the relevant changeover dates can be entered on
operating lines 144 and 145. The entry to be made is the earliest possible changeover
date. The weekday on which changeover occurs is always a Sunday.
If the start of summertime is given as "The last Sunday in March", the earliest possible
changeover date is March 25. The date to be entered on operating line 144 is then
25.03.
If no summer- / wintertime changeover is required, the 2 dates are to be set so that
they coincide.
Undertemperature
supervision
Example