![Siemens RUGGEDCOM RX5000 Installation Manual Download Page 42](http://html.mh-extra.com/html/siemens/ruggedcom-rx5000/ruggedcom-rx5000_installation-manual_381900042.webp)
Chapter 6
Certification
RUGGEDCOM RX5000
Installation Guide
34
Other Approvals
•
China RoHS 2
Administrative Measure on the Control of Pollution Caused by Electronic Information Products
A copy of the Material Declaration is available online at
https://support.industry.siemens.com/cs/ww/en/
view/109738831
.
Section 6.1.9
Other Approvals
This device meets the requirements of the following additional standards:
•
IEEE 1613
IEEE Standard Environmental and Testing Requirements for Communications Networking Devices in Electric
Power Substations
•
IEC 61850-3
Communications Networks and Systems for Power Utility Automation – Part 3: General Requirements
•
IEC 61000-6-2
Electromagnetic Compatibility (EMC) – Part 6-2: Generic Standards – Immunity for Industrial Environments
Section 6.2
EMC and Environmental Type Tests
The RUGGEDCOM RX5000 has passed the following EMC and environmental tests.
IEC 61850-3 EMC Type Tests
Test
Description
Test Levels
Severity
Levels
Enclosure Contact
+/- 8 kV
4
IEC 61000-4-2
ESD
Enclosure Air
+/- 15 kV
4
IEC 61000-4-3
Radiated RFI
Enclosure Ports
20 V/m
Note
a
Signal ports
+/- 4 kV @ 2.5 kHz
Note
a
DC Power ports
+/- 4 kV
4
AC Power ports
+/- 4 kV
4
IEC 61000-4-4
Burst (Fast Transient)
Earth ground ports
+/- 4 kV
4
Signal ports
+/- 4 kV line-to-earth,
+/- 2 kV line-to-line
4
DC Power ports
+/- 2 kV line-to-earth,
+/- 1 kV line-to-line
3
IEC 61000-4-5
Surge
AC Power ports
+/- 4 kV line-to-earth,
+/- 2 kV line-to-line
4
Signal ports
10 V
3
IEC 61000-4-6
Induced (Conducted) RFI
D.C Power ports
10V
3