RUGGEDCOM RX1100
Installation Guide
Chapter 4
Technical Specifications
Power Supply Specifications
33
Technical Specifications
The following sections provide important technical specifications related to the device and available modules:
•
Section 4.1, “Power Supply Specifications”
•
Section 4.2, “Failsafe Relay Specifications”
•
Section 4.3, “Copper Ethernet Port Specifications”
•
Section 4.4, “Fiber Ethernet Port Specifications”
•
Section 4.5, “Serial Port Specifications”
•
Section 4.6, “IRIG-B Output Specifications”
•
Section 4.7, “Operating Environment”
•
Section 4.8, “Mechanical Specifications”
Section 4.1
Power Supply Specifications
Input Range
Power Supply Type
Minimum
Maximum
Internal Fuse
Rating
ab
Isolation
Maximum Power
Consumption
c
12 VDC
24 VDC
10 VDC
36 VDC
6.3 A(F)
48 VDC
36 VDC
59 VDC
3.15 A(T)
1.5 kVDC
HI (125/250 VDC)
d
88 VDC
300 VDC
HI (110/230 VAC)
d
85 VAC
264 VAC
2 A(T)
4 kVAC, 5.5 kVDC
25 W
a
(F) denotes fast-acting fuse
b
(T) denotes time-delay fuse.
c
Power consumption varies based on configuration. 10/100Base-TX ports consume roughly 1 W less than fiber optic ports.
d
The HI power supply is the same power supply for both AC and DC.
Section 4.2
Failsafe Relay Specifications
Parameter
Value (Resistive Load)
Max Switching Voltage
30 VAC, 80 VDC
Rated Switching Current
0.3 A @ 30 VAC
1 A @ 30 VDC, 0.3 A @ 80 VDC