![Siemens RUGGEDCOM RSG2300 Installation Manual Download Page 49](http://html.mh-extra.com/html/siemens/ruggedcom-rsg2300/ruggedcom-rsg2300_installation-manual_379098049.webp)
RUGGEDCOM RSG2300
Installation Guide
Chapter 6
Certification
EMC and Environmental Type Tests
41
Test
Description
Test Levels
Severity Levels
IEC 61000-4-17
Ripple on DC
Power Supply
DC Power Ports
10%
3
Signal Ports
2 kV (Fail-Safe
Relay Output)
DC Power Ports
2 kV
Dielectric Strength
AC Power Ports
2 kV
Signal Ports
5 kV (Fail-Safe
Relay Output)
DC Power Ports
IEC 60255-5
HV Impulse
AC Power Ports
5 kV
a
Only applicable to functional earth connections separated from the safety earth connection.
IEEE 1613 EMC Immunity Type Tests
NOTE
The RUGGEDCOM RSG2300 meets Class 2 requirements for an all-fiber configuration and Class 1
requirements for copper ports.
Description
Test Levels
Enclosure Contact
+/- 2 kV, +/-4 kV, +/-8 kV
ESD
Enclosure Air
+/-4 kV, +/-8 kV, +/-15 kV
Radiated RFI
Enclosure Ports
35 V/m
Signal Ports
+/- 4 kV @ 2.5 kHz
DC Power Ports
+/- 4 kV
AC Power Ports
+/- 4 kV
Fast Transient
Earth Ground Ports
+/- 4 kV
Signal Ports
2.5 kV Common Mode @1MHz
DC Power Ports
2.5 kV common, 1 kV differential mode @ 1 MHz
Oscillatory
AC Power Ports
2.5 kV common, 1 kV differential mode @ 1 MHz
Signal Ports
5 kV (Fail-Safe Relay Output)
DC Power Ports
5 kV
HV Impulse
AC Power Ports
5 kV
Signal Ports
2 kV
DC Power Ports
2 kV
Dielectric Strength
AC Power Ports
2 kV
Damped Oscillatory
Magnetic Field
Enclosure Ports
100 A/m Peak
Summary of Contents for RUGGEDCOM RSG2300
Page 4: ...RUGGEDCOM RSG2300 Installation Guide iv ...
Page 12: ...RUGGEDCOM RSG2300 Installation Guide Chapter 1 Introduction Description 4 ...
Page 36: ...RUGGEDCOM RSG2300 Installation Guide Chapter 3 Communication Ports BNC Ports 28 ...
Page 46: ...RUGGEDCOM RSG2300 Installation Guide Chapter 5 Dimension Drawings 38 ...