RUGGEDCOM RUGGEDCOM RS940G
Installation Guide
Chapter 4
Technical Specifications
Power Supply Specifications
21
Technical Specifications
The following sections provide important technical specifications related to the device and available modules:
•
Section 4.1, “Power Supply Specifications”
•
Section 4.2, “Failsafe Alarm Relay Specifications”
•
Section 4.3, “Copper Ethernet Port Specifications”
•
Section 4.4, “Fiber Optic Ethernet Port Specifications”
•
Section 4.5, “Supported Networking Standards”
•
Section 4.6, “Operating Environment”
•
Section 4.7, “Mechanical Specifications”
Section 4.1
Power Supply Specifications
Input Range
Power Supply Type
Minimum
Maximum
Internal Fuse
Rating
ab
Isolation
Maximum Power
Consumption
c
88 VDC
300 VDC
4 kVAC
HI
85 VAC
264 VAC
2.0 A(T)
5.5 kVDC
24 VDC
10 VDC
36 VDC
48
36 VDC
72 VDC
3.15 A(T)
1.5 kVDC
18 W
a
(F) denotes fast-acting fuse
b
(T) denotes time-delay fuse.
c
Power consumption varies based on configuration.
Section 4.2
Failsafe Alarm Relay Specifications
Maximum Switching Voltage
Rated Switching Current
Isolation
30 VDC
2 A, 60 W
125 VDC
0.24 A, 30 W
125 VAC
0.5 A, 62.5 W
220 VDC
0.24 A, 60 W
250 VAC
0.25 A, 62.5 W
1500 V
rms
for 1 minute