Document No. 125-1009
Installation Instructions
February 10, 2020
Page 14 of 20
Siemens Industry, Inc.
Table 8. 600 Series BACnet Configuration Parameters*.
Parameter
Definition
Display
Value Range
Default
Extended Definition
P601
MS/TP MAC address
MS--TP MAC
0-255
255
MS/TP MAC address must be unique for the
entire network 1 to 254.
In systems that support and use Master Nodes
valid range to use is from 1 to 127.
In systems that support and are using auto
discovery leave value at default 255
NOTE:
When integrating with APOGEE
®
, set
this parameter to be a Master Node.
P602
Baud Rate
BAUD RATE
A
= Auto
9.6
= 9600
19.2 =19200
38.4 = 38400
57.6 = 57600
76.8 = 76800
115.2 =115200
A=Auto
This parameter wil
l set the network’s baud rate.
Auto value will match detected Baud Rate in
systems that support and are using auto
discovery leave value at default “A”
P603
Device Instance
DEV ID
0 - 4194303
4194303
Device Instance (unsigned integer 0-4194303)
In systems that support and are using auto
discovery leave value at default 4194303
P604
Max Master
MAX MASTER
1--127
127
Max Master
P605
Serial number
SER NR
Display Only
Display
Only
Display Serial number, 10 digit hex,
programmed in factory
P606
Max Info Frames
MAX FRAME
1-- 10
1
Max Info Frames
CAUTION:
* See the Energy Management System Network Plan before entering values in
the RDY2000BN 600 Series BACnet Configuration Parameters. Incorrect values
will prevent connection to the Energy Management System.
Table 9. 700 Series BACnet Configuration Parameters
Parameter
Definition
Display
Value Range
Default
Extended Definition
P701
Firmware
FIRMWARE
Display only
Display only
Display Firmware Version