3.13.4 Parameters of the Expert
level with diagnostics and
test
P
ar
am
et
er
Name
Factory setting
Range
R
D
G
40
0K
N
R
D
G
40
5K
N
D
ep
en
d
en
-
ci
es
Expert level
P30
Heat P-band Xp/switching diff
2 K
0.5…6 K
P31
Cool P-band Xp/switching diff
1 K
0.5…6 K
P32
Radiator P-band Xp/swi diff
2 K
0.5…6 K
Appl
P33
Dead zone Comfort mode
2 K
0.5…5 K
Appl
P35
Integral action time Tn
RDG400KN
RDG405KN
5 min
45 min
0…10 min
0…120 min
P46, P47
P36
H/C ch'over swi point cooling
16 °C
10…25 °C
P38
P37
H/C ch'over swi point heating
28 °C
27…40 °C
P38
P38 Input
X1
RDG400KN
(range 0..3 [ECO]..8)
RDG405KN
(range 0..3 [PROT]..10)
1: = Ext. sensor
0 = --- (no function)
1 = Room temp ext. sensor/
return air temp (AI)
2 = H/C changeover (AI/DI)
3 = Operat. mode contact [ECO],
window contact [PROT] (DI)
4 = Dewpoint sensor (DI)
5 = Enable electric heater (DI)
6 = Fault input (DI)
7 = Monitoring input (Digital)
8 = Monitoring input (Temp)
10 = Presence detector (DI)
P39
Normal position input X1
0 (NO)
0 = Normally open/open
1 = Normally closed/close
P38
P40 Input
U1
0
0 = No function
1 = Input for air damper position
2 = input CO
2
sensor
X
P42 Input
D1
RDG400KN
(range 0..3 [ECO]..7)
RDG405KN
(range 0..3 [PROT]..10)
3 =
Operating mode
contact (RDG400KN)
Window contact
(RDG405KN
0 = --- (no function)
2 = H/C changeover (DI)
3 = Operat. mode contact [ECO],
window contact [PROT] (DI)
4 = Dewpoint sensor (DI)
5 = Enable electric heater (DI)
6 = Fault input (DI)
7 = Monitoring input (Digital)
10 = Presence detector (DI)
P43
Normal position input D1
0 (N.O.)
0 = Normally open/open
1 = Normally closed/close
P42
P44
Actuator running time Y1/Y2
150 s
20…300 s
P46
P46 Output
Y1/Y2
On/Off (1)
0 = 3-position
1 = 2-position - ON/OFF
2 = 2-position - PWM
Appl
P47 Controller output VAV
0 = DC 0…10 V
0 = DC 0…10 V
1 = 3-position
Appl
P51
Flow temp limit floor heating
Off
Off, 10...50 °C
P38
P54 Fan overrun time
60 s
0…360 s
P63
Supply air limit value min
0%
0…P64 (%)
P64
Supply air limit value max
100%
P63...100 (%)
P65 Protection heating setpoint
8 °C
OFF, 5…WCoolProt;
WCoolProt = 40 °C max.
P66 Protection cooling setpoint
Off
OFF, WHeatProt… 40;
WHeatProt = 5°C min.
P68 Temporary Comfort mode
0 (= Off)
0...360 min
P02
P69 Temporary Comfort setpoint
Off
OFF = Disabled
ON = Enabled