45 / 87
Siemens
RDG400KN,RGD405KN Basic documentation
CE1P3192en
Building Technologies
2017-02-17
3.6.9 Setpoints and sequences
Comfort setpoint (w) is in the currently active heating or cooling sequence.
∂
If the supply air temperature is available (via KNX), the air
flow may also increase when the room temperature is
below the heating setpoint
∂
If no supply air temperature is available, the sequence for
air flow control is cooling only
The setpoints for Economy and Protection mode are below the Comfort setpoints
(heating) and above the Comfort setpoints (cooling).
They can be set via P11, P12 (Economy) and P65, P66 (Protection).
w
3
18
1D
1
27
T[
癈
]
w
HeatProt
w
CoolProt
w
HeatEco
w
CoolEco
Comfort mode
Economy/Protection mode
Application
Heating
Cooling
Heating
Cooling
Single-duct 1)
Single-duct with
electric heater/
radiator/floor
heating
Single-duct with
heating/cooling
coil
Heating and cooling
Heating and cooling
SW < 1.24/
device index < C
only:
Single-duct
with electric
heater/radiator/
floor heating
W = setpoint in Comfort mode
W
HeatEco/Prot
= setpoint heating in Economy or Protection mode
W
CoolEco/Prot
= setpoint cooling in Economy or Protection mode
Y = air/water sequence
T = room temperature
The dead zone can be adjusted via P33.
1) Single-duct: A dead zone can be set also. In this case, the diagram is the same as for single-duct
with electric heater
Changeover air
Economy, Protection
Y
T
W
HeatEco/Prot
Y
T
W
Y
T
W
CoolEco/Prot
Y
T
W
HeatEco/Prot
Y
T
W
Y
T
W
Y
T
W
CoolEco/Prot
Y
T
W
HeatEco/Prot
Y
T
W
Y
T
W
Y
T
W
CoolEco/Prot
Y
T
W
HeatEco/Prot
Y
T
W
Y
T
W