background image

Operating Instructions

en

RDG200KN
RDG260KN

RDG2..KN – Room thermostat with KNX communications allowing users to set both ideal temperature
and relative humidity. The thermostat offers the operating modes Comfort, Economy and Protection.
In addition, it can operate in Auto mode as per a schedule via KNX bus.
The fan operates either in Auto mode or at the selected speed in Manual mode.
Users can either use the factory settings or adjust settings as desired.

  Main display

  Operating mode

Operating mode selection

Protection mode

Fan speed selection

Economy mode

Escape

Comfort mode

Confirm parameters

Cooling mode

Outside temperature

Electric heater active

Relative humidity

Heating mode

Degrees Celsius or Fahrenheit

Manual changeover

Auto mode

Parameter

Temporary timer

Morning: 12-hour format (via bus);
Afternoon: 12-hour format (via bus)

Fault

Additional user information, such as outside
temperature, time of day from KNX bus, relative
humidity

Button lock

Condensation in room
(dewpoint sensor active) or
humidity control active

Digits for room temperature and setpoint display

Operating mode button

Automatic fan

Fan mode button

Fan speed I

Rotary knob

   Green leaf

Fan Speed II

Protection hospitality mode button

Fan Speed III

  Changing the room temperature

Turn the rotary knob clockwise to increase, or counterclockwise to decrease the
current room temperature setpoint.
Note: The setting range is 5...40 °C; it can be limited by parameters P013 and P016.
(for parameter settings, see Control parameters on page 2).

  Adjusting the fan speed

·

Press the right button repeatedly until the desired fan mode is reached.

·

In Auto mode

 , the fan speed is automatically selected by the thermostat

depending on setpoint and current room temperature.

·

In Manual mode, the fan operates independently and runs at the speed set by
the user: speed I / speed II / speed III.

Speed

I

Speed

II

Speed

III

  Changing the operating mode

1. Comfort mode

·

In Comfort mode, the thermostat maintains the room temperature at the setpoint
which can be adjusted with the rotary knob.

2. Economy mode

·

In Economy mode, the thermostat maintains the room temperature at a lower or
higher setpoint, thus saving energy and money.

·

The  thermostat  can  be  set  to  Economy  mode  either  by  pressing  the  operating
mode button if enabled (P002 =  2), or via an external signal (switch or KNX bus
command) such as keycard.

·

The Economy setpoints are factory-set to 15 °C for heating and 30 °C for cooling.
They can be adjusted via parameters P019 and P020 (for parameter settings, see
Control parameters on page 2).

3. Protection mode

·

In Protection mode, the thermostat stops operating. However, if the room
temperature drops below 8 °C, heating is switched on to protect the room against
frost.

·

The thermostat switches to Protection mode when the window contact (local or on
KNX) is activated.

The setpoints for Protection mode can be changed by your HVAC installer if desired:
Changes made by installer:

!

     Frost protection: _________ 

˚

C

Heating protection: __________ 

˚

C

4. Auto mode

·

In Auto mode, the thermostat automatically switches over between Comfort and
Economy mode as per the KNX bus.
If no schedule is available, Comfort replaces Auto.

 Important

: If setpoints are set to Off, there is no protective heating or cooling function.

Risk of frost!

  Green leaf indication

  The green leaf indication is an energy-efficient setting and indicates the end user settings.

Green leaf: Settings are within the
preset energy-efficient range.

Red leaf: Settings exceed the preset
energy-efficient range.
End users can press the red leaf and
return to the energy-efficient range.

  Reminder to clean filter, display of external faults

FIL *

AL1 *
AL2 *
AL3 *

This message reminds you to clean the filter on your HVAC equipment.
It appears after

!

 _______ "fan operating hours" and disappears when the thermostat is

set to Protection.
These fault messages tell you an external fault has occurred *:

AL1 :

!

 _______________________

AL2 :

!

 __________________________

AL3 :

!

 _______________________

* Needs to be configured by HVAC installer

  Button lock

·

  If the button lock function is enabled (parameter P028 = 2), pressing the right

button for 3 seconds locks or unlocks the buttons respectively.
Locked buttons are indicated by the key symbol .

·

  If “Auto lock” is configured (P028 = 1), the thermostat automatically locks the

buttons 10 seconds after the last adjustment.

  Commissioning

(by qualified HVAC installer)

To adapt the thermostat to your system and optimize control performance, a number of control

parameters can be adjusted. This can be done during operation, either via the buttons on the

thermostat or via a commissioning tool.

Reviews: