  Control parameters

To change control parameters, proceed as follows:

1. Press left and right buttons simultaneously for 3 seconds or until device beeps if buzzer function is

enabled (P030).

2.

Service level

: Release and within 0.5…4 seconds, press the right button again until “P001” is

displayed.

Expert level

: Release and within 0.5…4 seconds, press the left button again until the temperature

disappears. Turn the rotary knob counterclockwise minimum ½ rotation.

P050

 displays.

3. Select the required parameter by turning the rotary knob.
4. Press button  (OK). The current value of the selected parameter flashes and can be changed by

turning the rotary knob.

5. Press button  (OK) to confirm the adjusted value, or  (Esc) to cancel the change.

To adjust additional parameters, repeat steps 3 through 5, or press  (Esc) to quit parameter setting

mode.

Note: If password protection (needs to be done by HVAC installer) is enabled, users must enter the password to open
parameter setting mode. If the password is mistyped 5 times, the thermostat is locked and the password cannot be
entered for 5 minutes. Symbols

 and

 are displayed.

  Parameter list

No. Description

Factory setting

Setting range

Adj.

!

P001 Control sequence

2-pipe:
1 = Cooling only

4-pipe:
4 = Heating and

cooling

0 = Heating only
1 = Cooling only
2 = H/C changeover auto
3 = H/C changeover manual
4 = Heating and cooling

P002 Operation via room operating mode

selector

1

1 = Auto ** (Comfort) – Protection
2 = Auto ** - Comfort - Economy - Protection
3 = Auto ** (Comfort) - Protection Hospitality

P003 Operation via fan operating selector

0

0 = Auto - Manual
1 = Manual
2 = Auto - Manual - Protection
3 = Auto – Protection

P004 Unit

0

0 = °C (parameter in °C)
1 = °F (parameter in °F)

P006 Measured value correction

0 K

-5…5 K

P007 Humidity value correction

0

-10…0…10 %

P008 Standard display

0

0 = Room temperature
1 = Setpoint

P009 Additional display information

0

0 = --- (No display)
1 = °C and °F
2 = Outside temperature (via bus)
3 = Time of day (12 h) (via bus)
4 = Time of day (24 h) (via bus)
5 = Humidity

P010 Setpoint concept

1

1 = Comfort concept
2 = Energy saving concept

P011 Comfort basic setpoint

21 °C (70 °F)

5…40 °C (41…104 °F)

P013 Comfort setpoint minimum

5 °C (41 °F)

(P010 = 1): 5 °C (41 °F)...P016-1 K
(P010 = 2): 5 °C (41 °F)...P014-1 K

P014 Comfort setpoint maximum heating

21 °C (70 °F)

P013+1 K…P015-1 K

P015 Comfort setpoint minimum cooling

25 °C (77 °F)

P014+1 K…P016-1 K

P016 Comfort setpoint maximum

35 °C (95 °F)

(P010 = 1): P013+1 K...40 °C (104 °F)
(P010 = 2): P015+1 K...40 °C (104 °F)

P019 Economy heating setpoint

15 °C (59 °F)

OFF (0), 5 °C…P020 (41 °F…P020)
P020 = 40 °C max. (P020 = 104 °F max.)

P020 Economy cooling setpoint

30 °C (86 °F)

OFF (0), P019…40 °C (P019…104 °F)
P019 = 5 °C min. (P019 = 41 °F min.)

P024 Humidity setpoint high

50

OFF (0), P026 or 20…90 %

P026 Humidity setpoint low

OFF

OFF (0), 20…90 % or P024

P027

*** Electric heater when cooling

ON

ON = Enabled
OFF = Disabled

P028 Keypad

0

0 = Unlocked
1 = Auto lock
2 = Manual lock
3 = Lock the operating mode
4 = Lock the Setpoint shift
5 = Lock fan speed
6 = Lock operating mode and setpoint shift
7 = Lock operating mode and fan speed
8 = Lock setpoint shift and fan speed

P029 Fan: Dead zone Comfort mode

0

0 = Fan disable
1 = Low speed (Heat and Cool)
2 = Low speed (Cooling only)
3 = Fan disable Auto & Manual
4 = Low speed (Heat and Cool) Auto &

Manual
5 = Low speed (Cooling only) Auto & Manual

P030 Buzzer function

ON

ON = Enabled
OFF = Disabled

  **  When no time schedule via KNX exists, Auto equals Comfort.
  *** Parameter P027 is displayed only for application 2-pipe with electric heater.
  All temperature settings are in increments of 0.5 °C.

!

    Remember to record all changes!

Issued by
Siemens Switzerland Ltd
Smart Infrastructure
Global Headquarters
Theilerstrasse 1a
CH-6300 Zug
Tel. +41 58 724 2424
www.siemens.com/buildingtechnologies

© Siemens Switzerland Ltd, 2020

Technical specifications and availability subject to change without notice.

A6V11545973_en--_a

A5W00031435A_AA

2020-09-07

Siemens Smart Infrastructure

Reviews: