RDG100.., RDG110.., RDG160T.. Basic Documentation
CE1P3181en
Building Technologies
Functions
2015-07-29
P
ar
am
et
er
Name
Factory
setting
Range
R
D
G
11
0U
R
D
G
16
0T
U
D
ep
en
d
en
ci
es
Expert level
P52 Fan operation
1
0 = disabled
1 = enabled
2 = heating only
3 = cooling only
P53 Fan speed
3-speed
1 = 1-speed
2 = 3-speed
x
P52
P53 Fan speed
DC 0...10 V
1 = 1-speed fan
2 = 3-speed fan
3 = DC 0...10 V (ECM fan)
x
P52
DIP4
P54 Fan overrun time
(only when electric heater is used)
60 s
0...360 s
P52, Appl
P55 Switching point fan speed high
100%
80..100%
P52
P55
ECM fan max. output
ECM: 80%
ECM: fan min…100%
x
P52
P56 Switching point fan speed medium
65%
30...75%
P52
P56
ECM fan min. output
ECM: 30%
ECM: 1%...fan max.
x
P52
P57 Switching point fan speed low
10%
1...15%
P52
P57
ECM: Switching point fan
ECM:10%
ECM: 1..100%
x
P52
P58 Fan start booster
ON
ON: Enabled
OFF: Disabled
P52
P59 Fan min. on time
2 min.
1...6 min
P52
P60 Fan kick interval in Comfort mode
(time until next kick)
OFF
0…89 min, OFF
P52
P61 Fan kick interval in Economy mode
(time until next kick)
OFF
0…359 min, OFF
P52
P62 Clean filter reminder running time
OFF (0)
OFF, 100…9900 hours
P52
P63 Minimum supply air temperature
OFF
OFF, 32…P64 °F
x
P38, P40
P64 Maximum supply air temperature
OFF
OFF, P63…122 °F
x
P38, P40
P65 Protection heating setpoint
8 °C
OFF, 41…W Cool Prot;
(W Cool Prot = 104 °F max.)
P66 Protection cooling setpoint
OFF
OFF, W Heat Prot…104 °F ;
(W Heat Prot = 41 °F min.)
P67 Fan start delay
RDG110U
RDG160TU
0 s
0...180 s
0...360 s
P52, P46,
P47
P68 Extension Comfort period
OFF (0)
OFF(0); 15...360 min
P02
P69 Temporary setpoint Comfort mode
(see also Comfort setpoint P08)
OFF
OFF = disabled
ON = enabled
P70 Infrared receiver
ON
OFF = disabled
ON = enabled
x
P71 Reload factory settings
OFF
OFF = disabled
ON = reload start
P72
Output Q1 function
0
0 = No function
1= Switch OFF in Protection
2= Switch ON in H/C demand (2-pipe)
3= Switch ON in H demand (4-pipe)
4= Switch ON in C demand (4-pipe)
5= Status active sequence (H or C)
x
App
P73
Output Q2 function
0
0 = No function
1= Switch OFF in Protection
2= Switch ON in H/C demand (2-pipe)
3= Switch ON in H demand (4-pipe)
4= Switch ON in C demand (4-pipe)
5= Status active sequence (H or C)
x
App
P74
Output Q3 function
0
0 = No function
1= Switch OFF in Protection
2= Switch ON in H/C demand (2-pipe)
3= Switch ON in H demand (4-pipe)
4= Switch ON in C demand (4-pipe)
5= Status active sequence (H or C)
x
App
Parameter available
Parameter not available