4.7.8 2-stage heating or cooling
On 2-stage applications, the thermostat controls 2 valves or compressors in heating or
cooling mode or changeover (automatic or manual).
"Cooling only" is factory-set (P01=1).
In heating mode, the 1st stage is activated if the acquired temperature is below the
setpoint.
The 2nd stage is activated if the acquired room temperature drops below "setpoint"
minus "setpoint differential".
In cooling mode, the 1st stage is activated if the acquired temperature is above the
setpoint.
The 2nd stage is activated if the acquired room temperature rises above "setpoint"
plus "setpoint differential".
The diagrams below show the control sequence for 2-position control.
Heating mode (P01=0)
Cooling mode P01=1)
Changeover (P01=2 or P01= 3)
T[°C] Room temperature
w
Room temperature setpoint
YHC1 Control command "Stage 1"
YHC2 Control command "Stage 2"
SDH Switching differential "Heating" (P30)
SDC Switching differential "Cooling" (P31)
X
dz
Dead zone (P33)
w
D
Setpoint differential (P34)
2-stage heating
or cooling
Heating mode
Cooling mode
On/Off control