RDG100.., RDG110.., RDG160T.. Basic Documentation
CE1P3181en
Building Technologies
Functions
2015-07-29
4.15.1 Parameters of the "Service level" – Degree Celsius
P
ar
am
et
e
r
Name
Factory setting
Range
R
D
G
10
0
R
D
G
10
0T
R
D
G
10
0T
/H
R
D
G
11
0
R
D
G
11
0U
R
D
G
16
0T
R
D
G
16
0T
U
D
ep
en
d
en
ci
es
Service level
P01 Control
sequence
With 2-pipe/
2-stage:
1 = cooling only
With 4-pipe:
4 = H/C
0 = heating only
1 = cooling only
2 = H/C changeover manually
3 = H/C changeover automatically
4 = heating and cooling
P02
Operating mode profile (operating mode
button)
1
1 = (Auto) - Comfort – Protection
2 = (Auto) - Comfort - Economy - Prot
P01
3 = Comfort – Protection
4 = Comfort – Economy – Protection
x
x
P03 Fan mode selection
0
0 = Auto – Manual
1 = Manual
2 = Auto – Manual – Prot
P52
3 = Auto – Prot
x
x
x
x
P04
Selection of °C or °F
0 (°C)
0 = degrees Celsius (°C)
1 = degrees Fahrenheit (°F)
P05
Sensor calibration (internally, externally)
0 K
– 3...3 K
P06 Standard temperature display
0
0 = room temperature
1 = setpoint
P07 Display info line
(2nd line of LCD)
0
0 = --- (no display)
1 = °C and °F
0..1
x
x
0..1
x
P08 Comfort
setpoint
21 °C
5...40 °C
P09
Min. setpoint for Comfort mode
5 °C
5...40 °C
P10
Max. setpoint for Comfort mode
35 °C
5...40 °C
P11 Economy heating setpoint
15 °C
OFF, 5...WcoolE-saving;
(WcoolE-saving = 40 °C max.)
P12 Economy cooling setpoint
30 °C
OFF, WHeatEco...40 °C;
(WHeatEco = 5 °C min.)
P13
Electric heater in cooling mode
ON
ON: Enabled
OFF: Disabled
Appl
P14 Button lock function
0
0 = unlocked
1 = auto locked
2 = manual locked
P15
Fan stage in dead zone (Comfort)
0
0 = disabled
1 = stage 1 (heating and cooling)
2 = stage 1 (cooling only)
Parameter available
Parameter not available
Parameter display depends on selected application and function.
Note