RDF30U Room Temperature Controller with LCD 

Technical Instructions 

For Four-Pipe Fan Coil Units 

Document Number 155-335 

 

September 27, 2007 

Siemens Industry, Inc. 

Page 9 

 

 

Specifications, 
Continued 

Environmental Conditions 

Operation 

 

 

Temperature 

32°F to 122°F (0°C to 50°C) 

 

Humidity 

<95% rh 

Transport and storage 

 

 

Temperature 

-13°F to 158°F (-25°C to 70°C) 

 

Humidity 

<95% rh 

Agency Approvals 

UL Listing 

UL 873 

General 

Connection terminals 

Solid wires or prepared stranded 

 

 

 

wires 2 × 16 AWG or 1 × 14 AWG 

Weight   

0.5 lb (0.23 kg) 

Housing front color 

White, NCS S 0502-G (RAL 9003) 

Wiring Terminals 

 

Figure 4.  Wiring Terminals. 

1, 2 

24 Vac negative 

24 Vac positive 

Control valve output, 24 Vac 

Control  valve output, 24 Vac 

 

(inverse of output 4) 

Control output, second stage 

 

heating or cooling (NO contact) 

Measuring neutral, remote sensor 

Return air temperature sensor 

10 

Control output, Fan speed III, 24 Vac 

11 

Control output, Fan speed II, 24 Vac 

12 

Control output, Fan speed I, 24 Vac 

D1, 

Status input for potential-free 

GND

 

    

operating mode changeover switch 

Wiring Diagrams 

 

Figure 5.  Four-Pipe Fan Coil Units. 

B1 

Return air temperature sensor 

 

(QAH11.1) 

M1  

Three-speed fan 

N1 

Room temperature controller 

 

RDF30U 

S1 

External operating mode 

 

changeover switch 

SN 

24 Vac, negative 

SP 

24 Vac, positive 

Y1 

Zone valve for Heating mode 

Y2 

Zone valve for Cooling mode 

Summary of Contents for RDF30U

Page 1: ...ting mode changeover input for remote control Day Night Air movement control function for avoiding damage resulting from moisture Selectable installation and control parameters Display of room temperature or setpoint selectable Electronic minimum and maximum setpoint limits Operating voltage 24 Vac Application Typical use For controlling room temperature in individual rooms that are heated or cool...

Page 2: ...wing occurs leaving the heating or cooling sequence provided the Temperature dependent fan control function is activated manually changing to Standby provided no setpoints example for freeze protection are set and active activating an external operating mode changeover switch provided application conditions do not call for Economy mode turning off the controller s power supply Display If DIP Switc...

Page 3: ... the measured room temperature or the fan coil unit s return air temperature It detects if a QAH11 1 cable temperature sensor is connected to input 9 8 and then operates automatically according to that temperature Operating Modes Normal Mode Heating or Cooling mode with automatic changeover and manually selected fan speed III II or I In Normal mode the controller maintains the adjusted setpoint in...

Page 4: ...g operation without opening the unit In the event of a power failure all set control parameters will be maintained Settings The parameters can be changed as follows 1 Set the operating mode selector to Standby 2 Press buttons and simultaneously for a minimum of three seconds Release them and within two seconds press the button again for three seconds The display will show P01 3 Select the required...

Page 5: ... or switching differential heating NOTE This parameter is in degrees Kelvin 1 K 1 8 F 0 5 K to 4 K 1 F to 7 F in increments of 0 5 K 2 K 3 6 F P11 P band in Cooling mode or switching differential cooling NOTE This parameter is in degrees Kelvin 1 K 1 8 F 0 5 K to 4 K 1 F to 7 F in increments of 0 5 K 1 K 1 8 F P12 Dead zone in Normal mode 0 5 K to 10 K 1 F to 18 F in increments of 0 5 K 2 K 3 6 F ...

Page 6: ...nical Design The controller consists of two parts Plastic housing which accommodates the electronics the operating elements and the built in room temperature sensor Base The housing engages in the base and is secured with two screws The base carries the screw terminals The DIP switches are located at the rear of the housing Setting and Operating Elements Figure 2 RDF30U Components 1 Display of the...

Page 7: ... Changeover activated when switch is open 4 Output sequence Heating and cooling four pipe Two stage cooling Mounting Installation and Commissioning Notes Mounting location On a wall or inside the fan coil unit Do not mount in niches or bookshelves behind curtains above or near heat sources Do not mount in direct sunlight Mounting height is approximately 60 inches 1 5 m above the floor The connecti...

Page 8: ...eter P09 Specifications Power Supply Operating voltage 24 Vac 20 25 Frequency 50 60 Hz Power consumption 6 VA maximum Fan control outputs 12 11 10 24 Vac Rating 5 3 A maximum Valve control output 4 6 NO 24 Vac 55 3 A maximum Return air temperature sensor QAH11 1 safety class II status input 9 8 NTC resistor 3 k at 77 F 25 C Status input D1 and GND Contact sensing SELV 6 to 15 Vdc 3 to 6 mA Insulat...

Page 9: ...Terminals Figure 4 Wiring Terminals 1 2 24 Vac negative 3 24 Vac positive 4 Control valve output 24 Vac 5 Control valve output 24 Vac inverse of output 4 6 Control output second stage heating or cooling NO contact 8 Measuring neutral remote sensor 9 Return air temperature sensor 10 Control output Fan speed III 24 Vac 11 Control output Fan speed II 24 Vac 12 Control output Fan speed I 24 Vac D1 Sta...

Page 10: ...rademarks of their respective owners 2007 Siemens Industry Inc Siemens Industry Inc Building Technologies Division 1000 Deerfield Parkway Buffalo Grove IL 60089 1 847 215 1000 Your feedback is important to us If you have comments about this document please send them to SBT_technical editor us sbt siemens com Document No 155 335 Printed in the USA Page 10 Dimensions in Inches Millimeters Figure 6 R...

Reviews: