RDF30U Room Temperature Controller with LCD
Technical Instructions
For Four-Pipe Fan Coil Units
Document Number 155-335
September 27, 2007
Siemens Industry, Inc.
Page 7
Table 3. DIP Switches.
DIP Switch
No.
Description
Position ON (Factory Setting)
Position OFF
1
Fan control
Fan control is temperature-
independent in Normal mode
Fan control is temperature-
dependent in all operating
modes
2
Display of temperature or setpoint
Room (or return air) temperature
display
Setpoint display
3
Operating action of switch for external
operating mode changeover
Changeover activated when switch is
closed
Changeover activated when
switch is open
4
Output sequence
Heating and cooling (four-pipe)
Two-stage cooling
Mounting,
Installation and
Commissioning
Notes
▪
Mounting location: On a wall or inside the fan coil unit.
▪
Do not mount in niches or bookshelves, behind curtains, above or near heat
sources.
▪
Do not mount in direct sunlight.
▪
Mounting height is approximately 60 inches (1.5 m) above the floor.
▪
The connecting wires can be run to the controller from a recessed conduit box.
Figure 3. Acceptable Mounting Height in Inches.
▪
Check the positions of the DIP switches and change them, if required.
▪
After applying power, the controller makes a reset during which all LCD segments
flash, indicating that the reset has been correctly made. This takes about three
seconds. Then, the controller is ready to operate.
.
.
.