2.  the valve has been open for more than one minute (Parameter 19) 

NOTE: 

Output terminals 5 and 2 are the inverse of terminals 4 and 2. 

Cooling Mode 

Output terminals 6 and 2 (neutral) are open (0 Vac) when: 

1.  the measured room temperature is at half the switching differential below the 

Cooling mode setpoint (W + Xdz 

– 1/2 SDC), and 

2.  the valve has been open for more than one minute (Parameter P19). 

Output terminals 6 and 2 (neutral) are closed (24 Vac) when: 

1.  the measured room temperature is at half the switching differential above the 

Cooling mode setpoint (W + Xdz + 1/2 SDC), and 

2.  the valve has been closed for more than one minute (Parameter P20). 

 

 

Room temperature 

SDH  Switching differential, Heating 
SDC  Switching differential, Cooling 
Xdz 

Dead zone 

Room temperature setpoint 

YH 

Heating valve, 24 Vac control output 

YC 

Cooling valve, 24 Vac control output 

 

Figure 1.  Water-based Fan Coil 

Heating and Cooling Mode. 

 

Return Air Temperature 
(Optional) 

The RDF30U provides control based on the measured room temperature or the fan coil 
unit’s return air temperature. It detects if a QAH11.1 cable temperature sensor is 
connected to input 9-8 and then operates automatically according to that temperature. 

Operating Modes 

Normal Mode 

Heating or Cooling mode with automatic changeover and manually selected fan speed 
(III, II or I). In Normal mode, the controller maintains the adjusted setpoint in Heating 
mode and; in Cooling mode, a temperature level represented by the setpoint plus the 
dead zone. 

Economy Mode 

A potential-free operating mode changeover switch can be connected to status input 
D1-GND. When the switch closes its contact (due to an open window, for instance), the 
operating mode will change from Normal to Economy. In this operating mode, the 
relevant setpoints of heating or cooling are maintained (adjustable in Parameters P01 
[setback temperature for heating] and P02 [setback temperature for cooling]). The 
operating action of the switch (NC or NO) can be selected. 

Standby 

The relevant setpoints of heating and cooling are maintained when in Standb

y “ ” 

mode, provided those setpoints have been adjusted. The standby temperature setting 
for Heating mode in Parameter P03 is adjustable from 41°F to 68°F (5°C to 20°C) or 
“OFF” and the setting for Cooling mode in Parameter P04 is adjustable from 70°F to 
95°F (21°C to 35°C) or "OFF".  

Summary of Contents for RDF30U

Page 1: ...ting mode changeover input for remote control Day Night Air movement control function for avoiding damage resulting from moisture Selectable installation and control parameters Display of room temperature or setpoint selectable Electronic minimum and maximum setpoint limits Operating voltage 24 Vac Application Typical use For controlling room temperature in individual rooms that are heated or cool...

Page 2: ...wing occurs leaving the heating or cooling sequence provided the Temperature dependent fan control function is activated manually changing to Standby provided no setpoints example for freeze protection are set and active activating an external operating mode changeover switch provided application conditions do not call for Economy mode turning off the controller s power supply Display If DIP Switc...

Page 3: ... the measured room temperature or the fan coil unit s return air temperature It detects if a QAH11 1 cable temperature sensor is connected to input 9 8 and then operates automatically according to that temperature Operating Modes Normal Mode Heating or Cooling mode with automatic changeover and manually selected fan speed III II or I In Normal mode the controller maintains the adjusted setpoint in...

Page 4: ...g operation without opening the unit In the event of a power failure all set control parameters will be maintained Settings The parameters can be changed as follows 1 Set the operating mode selector to Standby 2 Press buttons and simultaneously for a minimum of three seconds Release them and within two seconds press the button again for three seconds The display will show P01 3 Select the required...

Page 5: ... or switching differential heating NOTE This parameter is in degrees Kelvin 1 K 1 8 F 0 5 K to 4 K 1 F to 7 F in increments of 0 5 K 2 K 3 6 F P11 P band in Cooling mode or switching differential cooling NOTE This parameter is in degrees Kelvin 1 K 1 8 F 0 5 K to 4 K 1 F to 7 F in increments of 0 5 K 1 K 1 8 F P12 Dead zone in Normal mode 0 5 K to 10 K 1 F to 18 F in increments of 0 5 K 2 K 3 6 F ...

Page 6: ...nical Design The controller consists of two parts Plastic housing which accommodates the electronics the operating elements and the built in room temperature sensor Base The housing engages in the base and is secured with two screws The base carries the screw terminals The DIP switches are located at the rear of the housing Setting and Operating Elements Figure 2 RDF30U Components 1 Display of the...

Page 7: ... Changeover activated when switch is open 4 Output sequence Heating and cooling four pipe Two stage cooling Mounting Installation and Commissioning Notes Mounting location On a wall or inside the fan coil unit Do not mount in niches or bookshelves behind curtains above or near heat sources Do not mount in direct sunlight Mounting height is approximately 60 inches 1 5 m above the floor The connecti...

Page 8: ...eter P09 Specifications Power Supply Operating voltage 24 Vac 20 25 Frequency 50 60 Hz Power consumption 6 VA maximum Fan control outputs 12 11 10 24 Vac Rating 5 3 A maximum Valve control output 4 6 NO 24 Vac 55 3 A maximum Return air temperature sensor QAH11 1 safety class II status input 9 8 NTC resistor 3 k at 77 F 25 C Status input D1 and GND Contact sensing SELV 6 to 15 Vdc 3 to 6 mA Insulat...

Page 9: ...Terminals Figure 4 Wiring Terminals 1 2 24 Vac negative 3 24 Vac positive 4 Control valve output 24 Vac 5 Control valve output 24 Vac inverse of output 4 6 Control output second stage heating or cooling NO contact 8 Measuring neutral remote sensor 9 Return air temperature sensor 10 Control output Fan speed III 24 Vac 11 Control output Fan speed II 24 Vac 12 Control output Fan speed I 24 Vac D1 Sta...

Page 10: ...rademarks of their respective owners 2007 Siemens Industry Inc Siemens Industry Inc Building Technologies Division 1000 Deerfield Parkway Buffalo Grove IL 60089 1 847 215 1000 Your feedback is important to us If you have comments about this document please send them to SBT_technical editor us sbt siemens com Document No 155 335 Printed in the USA Page 10 Dimensions in Inches Millimeters Figure 6 R...

Reviews: