Technical Instructions 

RAB20 Series Two-pipe Fan Coil Room Thermostat 

Document Number 155-526P25 
March 2, 2007 

Page 2

  

Siemens Building Technologies, Inc. 

 

Operation 

Heating Mode 

If the room temperature falls below the selected setpoint, the heating contact is closed. 

Cooling Mode 

If the room temperature rises over the selected setpoint, the cooling contact is closed. 

Fan Speed 

The fan control speed can be controlled two ways: 

 

Manually, using the three-speed fan switch on the thermostat cover for continuous 

operation.   (Low),   (Medium), 

 (High). 

 

Automatically, by switching to the selected fan speed using the thermostat for 
controlled operation. Prior to commissioning, the jumper position corresponding to 
the thermostat function must be selected. 

 

There are three jumper position choices on the printed circuit board: 

Fan Release Setting 

SR1 
SR2 
SR3 

Select fan speed as continuous operation

Auto

         Fan is switched with the cooling valve 

Auto

         Fan is switched with the heating valve 

 

Ventilation 

When the ventilation function ( ) is selected (on the RAB20.1.. only), the heating and 
cooling contacts are always open and the fan works at the selected speed. 

Changeover 

Heating/cooling changeover is automatic, based on room temperature. Changeover is 
achieved externally using an SPDT aqua sensor (not included) wired between 
Terminals W, Y and the zone valve to change switch action. 

Adjustments 

The required temperature can be selected by a rotating setpoint adjuster on the front of 
the thermostat. 

High and low setpoint limit stops can be engaged to limit temperature range. 

 

Table 1.  Product Numbers. 

 

Mounting Style 

Product 
Number 

Description 

RAB20UW 

Heating or cooling; degrees Fahrenheit and 
Celsius; two-pipe auto changeover 

Electrical Wall 

Box (with wall 

box adapter) 

RAB20.1UW  Heating or cooling; degrees Fahrenheit and 

Celsius; two-pipe auto changeover; fan only 
function 

RAB20U 

Heating or cooling; degrees Fahrenheit and 
Celsius; two-pipe auto changeover 

Drywall 

RAB20.1U 

Heating or cooling; degrees Fahrenheit and 
Celsius; two-pipe auto changeover; fan only 
function 

 

Summary of Contents for RAB20 Series

Page 1: ...ting voltage Two mounting styles electrical wall box or drywall Wall plate adapter ARG70 included with electrical wall box mount styles Application The RAB20 is used in heating or cooling systems with external automatic changeover devices aquastats to maintain the selected room temperature Typically used in commercial high rise and light industrial buildings in conjunction with Fans Zone valves Th...

Page 2: ...alve Auto Fan is switched with the heating valve Ventilation When the ventilation function is selected on the RAB20 1 only the heating and cooling contacts are always open and the fan works at the selected speed Changeover Heating cooling changeover is automatic based on room temperature Changeover is achieved externally using an SPDT aqua sensor not included wired between Terminals W Y and the zo...

Page 3: ...Off Weight 5 oz 0 14 kg Dimensions 3 80 4 45 1 68 inches 96 4 113 1 42 8 mm Color Ivory white with gray selector knobs Ambient Conditions Operation Temperature 32 F to 122 F 0 C to 50 C Relative humidity 95 Transport Storage Temperature 4 F to 122 F 20 C to 50 C Relative humidity 95 Wiring Screw terminals for wires of 2 16 AWG or 1 14 AWG minimum 20 AWG Housing Material Plastic Enclosure rating NE...

Page 4: ...st be de energized and the operating voltage checked before opening An ARG70 wall plate adapter provided with electrical wall box mount models must be used to mount to a 2 4 inch or 4 4 inch electrical wall box An ARG70 wall plate adapter must be used to meet UL and cUL requirements The thermostat must be mounted on a flat wall All local electrical regulations must be complied with If there are th...

Page 5: ...ion sensitive 10 Pull the wiring through the sub base 11 Position thermostat housing over the two mounting lugs located at the top of the sub base and press down on cover until bottom lugs snap in place 12 Terminate wires per wiring instructions on the inside of thermostat cover Optional To set limit stops remove gray tabs located on the setpoint knob and position high and low stops around perimet...

Page 6: ...hermostat base and push up to remove cover 3 Using the four screws provided fasten wall box adapter 3 to plaster ring 2 supplied by others 4 Pull wires through plaster ring 2 5 Flex adapter mask 4 and snap in place inside wall box adapter 3 6 Fasten sub base 5 included with thermostat to wall box adapter assembly 3 and 4 with the two screws provided 7 Follow Drywall Mounting Steps 7 through 16 The...

Page 7: ...rom the thermostat base and push up to remove cover 3 Using the two screws provided fasten wall box adapter 3 to plaster ring 2 supplied by others 4 Pull wires through plaster ring 2 5 Flex adapter mask 4 and snap in place inside wall box adapter 3 6 Fasten sub base 5 included with thermostat to wall box adapter assembly 3 and 4 with the two screws provided 7 Follow Drywall Mounting Steps 7 throug...

Page 8: ...S N1 G3 TH0508R3 Y I II III G2 G1 L ZV W AS Aqua sensor by others G1 Control output fan speed I Low G2 Control output fan speed II Medium G3 Control output fan speed III High L Operating voltage M1 3 speed fan N Neutral N1 Room thermostat W Valve output heating Y Valve output cooling ZV Zone valve Figure 5 Wiring W T F ON OFF SP SD TH0488R3 Heating Mode Y T F ON OFF SP SD TH0489R2 Cooling Mode SD ...

Page 9: ...lo Grove IL 60089 4513 U S A Your feedback is important to us If you have comments about this document please send them to SBT_technical editor us sbt siemens com Dimensions Dimensions in inches millimeters 3 80 96 4 4 45 113 1 1 68 42 8 TH0495R2 Figure 7 RAB20 Unit 1 18 30 0 66 16 9 2 56 65 1 9 7 5 0 0 5 1 1 3 2 56 65 0 51 13 1 18 30 1 38 35 0 46 11 8 1 00 25 5 3 9 99 3 38 86 Ø 0 14 3 6 Ø 0 25 6 ...

Reviews: