3/4

Siemens Building Technologies

Room temperature sensors QAA24, QAA25, QAA26, QAA27

CM1N1721E

HVAC Products

12.07.2003

 AEROGYR™ RWI65...

When using the 

QAA26

 in connection with the RWI65…, the latter must be set to

the setpoint setting range "Heating". In that case, the setpoint of "Heating" on the
RWI65... must be set to 20 °C and additionally, the following must be set:

  Data point 44 to –15 K and data point 45 to + 15 K for RWI65.01

or

  Commissioning data point 9 to –15 K and commissioning data point 10 to +15 K

for RWI65.02

  When using the 

QAA27

, the setpoint adjustment knob must be set to its centre posi-

tion. Additionally, the following must be set:

  Data point 44 to –4 °C and data point 45 to +5 °C for RWI65.01. The offset at data

point 50 must be corrected until data point 2 has value 0.

  Commissioning data point 9 to –15 °C and commissioning data point 10 to +15 °C

for RWI65.02. The offset at commissioning data point 15 must be corrected until
normal data point 2 has value 0.

 POLYGYR

®

 RCM6..., RCE6... and RWF...

For averaging with two temperature sensors and a POLYGYR

® 

controller, the sen-

sors need to be connected in series and the controller requires a setting range insert
AZW61.119-tx50.
If the 

QAA25

 is used with a shift controller, the sensor's range (0...50 °C) is required

for calculating the authority

 CLASSIC RKN…

Setpoint adjustments via 

QAA27 

is possible only with controllers RKN8-L, RKN88-L,

RKN-W and RKN88T.

Fitting and installation notes

Location: On an inner wall of the space to be heated or air conditioned. Not in reces-
ses, shelves, not behind curtains, not opposite or near heat sources.
The unit must not be exposed to direct solar radiation.

The end of the conduit at the sensor must be sealed to prevent false measurements
due to draughts through the conduit.

The permissible ambient conditions should be observed.

Installation instructions are printed on the packing.

Technical data

Range of use

0...50 °C

Setting range

refer to «Type summary»

Max. permissible line lengths
and measured value errors

refer to «Engineering notes»

Connection terminals for
cross-sectional areas of

2 x 1.5 mm

2

 or 1 x 2.5 mm

2

Degree of protection

IP 30 to EN 60 529

Safety class

III to EN 60 730

Operation to 

IEC 721-3-3

Climatic conditions

class 3K5

 Temperature 

0...50 

°C

Humidity 

< 85 % r. h.

Transport to 

IEC 721-3-2

Climatic conditions

class 2K3

Temperature

25...+ 65 °C

Humidity

< 95 % r. h.

Mechanical conditions

class 2M2

 conformity to

EMC directive 89 / 336 / EEC

General data

Connection terminals

Protective data

Environmental conditions

Norms and standards

Summary of Contents for QAA24

Page 1: ...ield of application Acquisition and adjustment of room temperature Type summary Type reference Description QAA24 Room temperature sensor QAA25 Room temperature sensor with setpoint adjuster setting range 5 35 C QAA26 Room temperature sensor with setpoint adjuster setting range 5 30 C QAA27 Room temperature sensor with setpoint adjuster setting range 3 K Ordering When ordering please give name and ...

Page 2: ...ed from the rear concealed wiring or from below or above surface run wires through knock out openings The units consist of two major sections Casing and baseplate Both snap together but can be detached again The casing accommodates the temperature sensing element and depending on the type of unit various setting and operating elements The ba seplate carries the connecting terminals only with QAA25...

Page 3: ... AZW61 119 tx50 If the QAA25 is used with a shift controller the sensor s range 0 50 C is required for calculating the authority CLASSIC RKN Setpoint adjustments via QAA27 is possible only with controllers RKN8 L RKN88 L RKN W and RKN88T Fitting and installation notes Location On an inner wall of the space to be heated or air conditioned Not in reces ses shelves not behind curtains not opposite or...

Page 4: ...rom serie B on with thin film element QAA25 QAA26 QAA27 Setpoint setting range 5 35 C 5 30 C 3 K Resistance range 95 685 Ω 1000 1195 Ω 1000 1175 Ω Resistance value at setpoint 0 K 1091 Ω 10 C 193 9 Ω 1039 Ω 20 C 390 0 Ω 1118 Ω 25 C 488 3 Ω 1157 Ω 30 C 586 7 Ω 1195 Ω Internal diagram B M LG Ni 1000 1721G01 1721G02 LG Ni 1000 R B M LG Ni 1000 B M R M 1721G03 B1 Room temperature measuring signal M Me...

Reviews: