Siemens Building Technologies

Room temperature sensors QAA24, QAA25, QAA26, QAA27

CM1N1721E

HVAC Products

12.07.2003

Equipment combinations

Type reference

For use with systems/units

QAA24

All systems/units that are capable of acquiring and
handling LG-Ni 1000 signals, such as:
UNIGYR

®

/VISONIK

®

, via a measured value module (measu-

red value input for temperature sensors LG-Ni 1000);
Synco™200, Synco™700; AEROGYR™ RWI65...;
TEC™ RCE9...; POLYGYR

®

 RCM6..., RCE6..., RWF...,

RWX... and RWC...; CLASSIC; DESIGO30

QAA25

Synco™200, Synco™700; POLYGYR

®

 RCM6..., RCE6...,

RWF..., RWX... and RWC...

QAA26

UNIGYR

®

/VISONIK

®

, via a measured value module (measu-

red value input for temperature sensors LG-Ni 1000);
AEROGYR™ RWI65...; TEC™ RCE9...

QAA27

Synco™200, Synco™700; CLASSIC RKN…;
DESIGO30 RCK...IB and RCH...IB; AEROGYR™ RWI65...

Mechanical design

The units have been designed for wall mounting. They are suitable for use with most
commercially available recessed conduit boxes. The cables can be introduced from the
rear (concealed wiring) or from below or above (surface-run wires) through knock-out
openings.
The units consist of two major sections: Casing and baseplate. Both snap together but
can be detached again. The casing accommodates the temperature sensing element
and, depending on the type of unit, various setting and operating elements. The ba-
seplate carries the connecting terminals.

(only with QAA25, QAA26 and QAA27)

Front

Rear

1

2 3

17

21

Z01

°C

1

Setting knob for infinite setpoint adjustment

2

Pin for mechanical maximum limitation of setpoint setting range

3

Pin for mechanical minimum limitation of setpoint setting range

For the permissible lengths of lines and measured value errors, refer to «Basic
System Data» of the respective control system.

Engineering notes

For the permissible lengths of lines and measured value errors, refer to «Basic
System Data» of the respective control system.

 UNIGYR

®

/VISONIK

®

When using the 

QAA26

, both the temperature sensor and the setpoint setting unit

must be connected to a measured value input (B...) of the measured value module
(PTM1.2R1K).

.
.
.
.
.
.

.
.
.

Setting and operating
elements

Legend

Disposal

Summary of Contents for QAA24

Page 1: ...ield of application Acquisition and adjustment of room temperature Type summary Type reference Description QAA24 Room temperature sensor QAA25 Room temperature sensor with setpoint adjuster setting range 5 35 C QAA26 Room temperature sensor with setpoint adjuster setting range 5 30 C QAA27 Room temperature sensor with setpoint adjuster setting range 3 K Ordering When ordering please give name and ...

Page 2: ...ed from the rear concealed wiring or from below or above surface run wires through knock out openings The units consist of two major sections Casing and baseplate Both snap together but can be detached again The casing accommodates the temperature sensing element and depending on the type of unit various setting and operating elements The ba seplate carries the connecting terminals only with QAA25...

Page 3: ... AZW61 119 tx50 If the QAA25 is used with a shift controller the sensor s range 0 50 C is required for calculating the authority CLASSIC RKN Setpoint adjustments via QAA27 is possible only with controllers RKN8 L RKN88 L RKN W and RKN88T Fitting and installation notes Location On an inner wall of the space to be heated or air conditioned Not in reces ses shelves not behind curtains not opposite or...

Page 4: ...rom serie B on with thin film element QAA25 QAA26 QAA27 Setpoint setting range 5 35 C 5 30 C 3 K Resistance range 95 685 Ω 1000 1195 Ω 1000 1175 Ω Resistance value at setpoint 0 K 1091 Ω 10 C 193 9 Ω 1039 Ω 20 C 390 0 Ω 1118 Ω 25 C 488 3 Ω 1157 Ω 30 C 586 7 Ω 1195 Ω Internal diagram B M LG Ni 1000 1721G01 1721G02 LG Ni 1000 R B M LG Ni 1000 B M R M 1721G03 B1 Room temperature measuring signal M Me...

Reviews: