Document No. 129-477
Installation Instructions
November 15, 2017

Page 2 of 4

Siemens Industry, Inc.

Mounting Information

Always mount the room unit vertically.

Locate the room unit:

 

according to design specifications and local
regulations.

 

where the air circulates around it freely (not in
recessed areas or behind doors).

 

allowing a minimum of 4 inches (10 cm) free
space above and below for proper airflow, the
front cover removal tool, and the computer
communication cable.

 

away from drafts caused by doors, windows,
outside walls, air registers, pipes, return air
plenums, and so on.

 

away from heat sources such as strong lights,
fireplaces, direct sunlight, and so on.

 

on an inside wall (preferably), about 5 feet
(1.5 m) above the finished floor, or per code
(ANSI, ADA, or local regulation).

Drywall Mounting (No Rough-in),
Typical

Base Plate Mounting and Wiring

1.  Mark the center (cable) hole and the mounting

hole locations, using the temperature sensor base
plate as a template. See Figure 3.

2.  Drill two 3/16-inch (4.8 mm) mounting holes and

mount the two plastic wall anchors flush to below
the wall surface for stable mounting of the device.

3.  Cut a 1-inch (25 mm) center hole with a hole saw.

NOTE:

It is recommended that you use the
optional insulating gasket on the back of
the Sensor Base for hollow wall
installations.

When applying the adhesive-backed
gasket to the back of the Sensor Base,
orient the gasket so that the cut-out
arrow portion of the gasket is in the
upper left-hand quadrant of the Sensor
Base. The Sensor Base has an

UP

arrow molded into the surface in the
same quadrant location (see Figure 6).

Figure 2.  Insulating Gasket.

4.  Pull about three inches (75 mm) of the cable through

the hole in the base plate.

5.  Mount the room unit base plate on the wall, noting the

UP

 arrow:

NOTE:

If required, position the back plate behind the
room unit base, aligning the top and bottom
mounting holes, prior to mounting to the wall:

a.  Install the two mounting screws provided, but do

not tighten.

b.  Level the room unit base plate for appearance.

c.  Tighten the two mounting screws to the room unit

base plate.

6.  Cut the cable, leaving about three inches (75 mm) on

the room unit side of the drywall. Ensure that pin
Number 1 connects to the same wire at each end of
the cable.

NOTE:

See Figure 2 for details on optional Gasket
application.

Figure 3.  Drywall Mounting (No Rough-in), Typical.

Summary of Contents for QAA2212.*W*N

Page 1: ...N Accessories AQA2200 INTL Room Unit Back Plate 10 pack 563 102 GSKT KIT Room Sensor Insulating Gasket 10 pack For hollow wall installations Caution Notations CAUTION Equipment damage or loss of data may occur if you do not follow a procedure as specified Expected Installation Time 20 minutes Item Number 129 477 Rev JA Required Tools Sizes 1 and 2 Phillips screwdrivers Small and medium flat blade ...

Page 2: ...l surface for stable mounting of the device 3 Cut a 1 inch 25 mm center hole with a hole saw NOTE It is recommended that you use the optional insulating gasket on the back of the Sensor Base for hollow wall installations When applying the adhesive backed gasket to the back of the Sensor Base orient the gasket so that the cut out arrow portion of the gasket is in the upper left hand quadrant of the...

Page 3: ...se plate by first hooking the room unit s front to the top latches and then rotating the cover downward until it latches 4 Loosen the safety set screw at the bottom of the base one or two revolutions to lock the cover to the base Be careful not to loosen too far as the screw can be completely removed from the base Electrical Box and Rough in Mounting Typical 1 If a locator is attached to the rough...

Page 4: ...it is powered by isolated DC Where power is current limited up to 300 mA it is not required to earth ground the controller isolated common Room unit DC GND must be connected to the controller common CAUTION Follow manufacturer s Installation Instructions and Wiring Guidelines for connecting the controller to the room unit For Siemens Controllers APOGEE Controllers with common already earth grounde...

Reviews: