4 / 10
Siemens
PXG3... BACnet router for Ethernet - LONWORKS - MS/TP
CM1N9270en_10
Building Technologies
2017-10-16
LEDs
RUN
FLT
HMI/Tool
LED
Color Activity
Function
RUN
Green
•
Continuously ON
•
Continuously OFF
•
Flashing
•
Device ready.
•
At least one internal power supply out
of range.
•
Start-up of device.
FLT
Red
•
Continuously OFF
•
Continuously ON
•
Flashing
•
OK
•
HW fault or program fault.
•
Incorrect or corrupt FW.
INF
--
--
(Not used)
COM1 Yellow
•
Flashing
•
Sends MS/TP packages.
COM2 Yellow
•
Flashing
•
Sends L
ON
W
ORKS
packages
(PXG3.L only).
SVC
Red
•
Continuously OFF
•
Continuously ON
•
Flashing
•
Flashing per wink
command *)
•
Configured.
•
Defective Hardware.
•
Unconfigured.
•
Physical identification of the router.
927
0Z
05
8 7 6 5 4 3 2 1
Ethernet
1 / 2
Green
•
Continuously ON
•
Continuously OFF
•
Flashing
•
Link active
•
Link inactive
•
Network activity
Yellow
•
Continuously ON
•
Continuously OFF
•
Link 100 Mbps
•
Link 10 Mbps
*) Wink command
pattern:
2s
1s
21s
5 Hz
5 Hz
9222z02
2s
1s
1
9270
z03
Button
Press
Description
1
•
Short
Physical identification on the network (Ethernet).
Proceed as follows to reset the device to a
factory state
:
1. Power off device.
2. Power on device.
3. Wait for all LEDs to light up and turn off again,
then push the SVC button.
4. Keep SVC button pressed until all LEDs light up, then release.
Up to Desigo V6_SP (FW V01.15.15.144)
: Keep SVC button
pressed until the green RUN LED flashes, then release.
5. Wait for device to fully start up unconfigured
(RUN LED on, SVC LED flashes).
Any device passwords and other settings are lost.
Service button