7 / 10
Siemens
PXG3... BACnet router for Ethernet - LONWORKS - MS/TP
CM1N9270en_10
Building Technologies
2017-10-16
Assignment as per
EN 60730
Operation of automatic controller
Degree of pollution
Design type
Type 1
2
Protection class III
Housing protection
standard
Protection type as per EN 60529
Front parts in the DIN section
Terminal part
IP30
IP20
Ambient conditions
Operation
Climatic conditions
Temperature
Humidity
Mechanical conditions
As per IEC 60721-3-3
Class 3K5
–5 ... 50 °C
5…95% r.h. (non-condensing)
Class 3M2
Transport
Climatic conditions
Temperature
Humidity
Mechanical conditions
As per IEC 60721-3-2
Class 2K3
-25...70 °C
5…95% r.h. (non-condensing)
Class 2M2
Standards, directives, and
approvals
Product standard
EN 60730-1 Automatic electrical controls for
household and similar use
Product family standard
EN 50491-x General requirements for Home
and Building Electronic Systems
(HBES) and Building Automation
and Control Systems (BACS)
Electromagnetic compatibility (Applications) For use in residential, commerce,
light-industrial and industrial
environments
EU conformity (CE)
CM1T9270xx *)
UL certification (US)
RCM-conformity (EMC)
CM1T9222en_C1 *)
EAC conformity
Eurasia conformity
Environmental compatibility Product environmental declaration (contains
data on RoHS compliance, materials
composition, packaging, environmental
benefit, disposal)
CM1E9270 *)
Color
Housing
RAL 7035 (light-gray)
Dimensions
Housing as per DIN 43880, see dimensions
Weight
Without/with packaging
286 g / 332 g
*) The documents can be downloaded at