Testing Static Trip III Devices
7
POWER CONTROL in a clockwise direction. This is a five turn
control arranged for 50 Hz operation so a noticeable deadband
is evident at zero output and 60 Hz. Increase the current until
the LONG TIME pick-up light comes ON. This should be at
.275 10%. The sampling rate of the ammeter is
such that the control must be moved very slowly to accurately
determine the pick-up current of the trip device. The pick-up
is always 110% of long time setting.
5. Decreasing the current should cause the light to go out.
6. Repeat the tests for the other phases and settings and
compare with Table 1.
Table 1
Long Time Element Calibrated Current Settings
Ground Element Calibrated Pickup Settings
Sensor
Rating
(Pri-Amps)
.5
.55
.6
.65
.7
.75
.8
.85
.9
.95
1.0
Sensor
Rating
Primary
Amps
20%
30%
40%
50%
60%
150
75
82.5
90
97.5
105
112.5
120
127.5
135
142.5
150
150
30
45
60
75
90
200
100
110
120
130
140
150
160
170
180
190
200
200
40
60
80
100
120
300
150
165
180
195
210
225
240
255
270
285
150
300
60
90
120
150
180
400
200
220
240
260
280
300
320
340
360
380
400
400
80
120
160
200
240
600
300
330
360
390
420
450
480
510
540
570
600
600
120
180
240
300
360
800
400
440
480
520
560
600
640
680
720
760
800
800
160
240
320
400
480
1200
600
660
720
780
840
900
960
1020
1080
1140
1200
1200
240
360
480
600
720
1600
800
880
960
1040
1120
1200
1280
1360
1440
1520
1800
1600
320
480
640
800
960
2000
1000
1100
1200
1300
1400
1500
1600
1700
1800
1900
2000
2000
400
600
800
1000
1200
3200
1600
1760
1920
2080
2240
2400
2560
2720
2880
3040
3200
3200
400
600
800
1000
1200
4000
2000
2200
2400
2600
2800
3000
3200
3400
3600
3800
4000
4000
400
600
800
1000
1200
Secondary
Current
Amps
.25
.275
.30
.325
.35
.375
.40
.425
.45
.475
.50
Available Models
RMS-TI(T). Long Time and Instantaneous
RMS-TIG(T,Z) Long Time, Instantaneous and Ground Fault
RMS-TS(T,Z) Long Time and Short Time
RMS-TSG(T,Z) Long Time, Short Time and Ground Fault
RMS-TSI(T,Z) Long Time, Short Time and Instantaneous
RMS-TSIG(T,Z) Long Time, Short Time, Instantaneous and
Ground Fault Devices with (T,/Z) designation include
optional targets (T) and/or zone interlocking (Z).
General Notes
1.
The “Tripping XFMR Rating” STATIC TRIP III represent
the primary current in amperes. The secondary rated
value is one half ampere.
2.
The current settings of the long time element are switch
selectable and are calibrated at points .5 through 1.0 as
shown in the rating table. Pickup is 1.1 times the setting.
3.
The pick-up setting of the short time delay element is
switch selectable and is calibrated at 2,3,4,5,6,7,8 and
12 multiples of the long time setting.
4.
Instantaneous calibration at 2,4,6,8, 12 and 15 multiples
of tripping XFMR rating.
5.
The pick-up settings of the ground elements are switch
selectable and are calibrated in multiples of the tripping
transformer rating as shown in the rating table.
6
The long time element has 5 bands which are field
selectable. The time delay at 6 multiples of pick-up is as
follows:
Band 1 —3.5 seconds Band 4—17 seconds
Band 2—6.0 seconds Band 5—30 seconds
Band 3—10 seconds
7.
The ground element has 3 bands which are calibrated at
1, 25 and 4 seconds.
8.
The short time element has 5 time bands
9.
The maximum interrupting time is the maximum length
of time that fault current flows, including arcing time.
10. The lower limit of ground fault recognition is 25 amperes
for RL-800 breakers and 40 amperes for an RL-1600
breaker.