18
Testing First Generation Trip Devices
Connections—
Use Cord Set 1 8-732-1 84-506
Phase Selector Switch on phase 1, for all tests.
The connections to the first generation trip devices terminate
on an 8 or 9 point terminal block mounted on the side of the
device. See Figure 8. To allow using the test set plugs to
connect to this terminal block, alligator clips are furnished
with the test set to clip onto the terminal block screws. Four
of the clips accept the four banana plugs and three accept
the pin plugs for the pick-up lights. The bottom line of Table
3 gives the calibrated settings for secondary amperes for the
first generation trip devices and on the same page, available
models are listed and described . Figures 13, 14, 15, 16 and
17 are the time current characteristic curves for the various
models. Connections from the test set are different for
different models and are shown in Figures 9 through 12.
It will be helpful to note certain differences between these
static trips and STATIC TRIP II devices: (1) there are three
Long Time Pick-Up knobs, one for each phase, instead of
one common knob as on STATIC TRIP II (2). There are only
three Long Time Bands instead of 6 and they are marked
“Maximum,” “Intermediate,” and “Minimum.” On some mod-
els, no long time band adjustment is available and the device
is marked to show which time band it contains. (3) The
Instantaneous Pick-Up is
Table 3
Breaker Type
Models A3, AG2, 4WAG D2 DG1 4WDG
Tripping
Transformer
Group No.
Models AG2 and DG1
Models 4WAG and 4WDG
Long Time Delay Elements Available
Pick-Up Settings (Amperes)
Long Time Delay Element
Available Ground Fault Settings
(Amperes)
Inst. or Short Time Delay
Available Ground Fault Settings
Amperes)
Percent of A" Pick-Up
Percent of A" Pick-Up
A
B
C
D
E
20%
40%
60%
80%
20%
40%
60%
80%
LA-600
40
50
60
70
80
I
-
-
-
-
-
-
-
LA-600
75
95
110
130
150
II
-
-
-
-
-
30
45
60
LA-600 LA-1600
125
155
175
220
250
III
-
-
-
-
25
50
75
100
LA-600 LA-1600
200
250
300
350
400
IV
40
80
120
160
40
80
120
160
LA-600 LA-1600
300
375
450
525
600
V
60
120
180
240
60
120
180
240
LA-600 LA-1600
400
500
600
700
800
V-x
80
160
240
320
80
160
240
320
LA-1600
500
625
750
875
1000
VI
100
200
300
400
100
200
300
400
LA-1600
800
1000
1200
1400
1600
Vll
160
320
480
640
160
320
480
640
LA-1600
1000
1250
1500
1750
2000
VII-x
200
400
600
800
200
400
600
800
LA-3000
1200
1500
1800
2100
2400
VIII
240
480
720
960
240
480
720
960
LA-3000 LA-4000
2000
2500
3000
IX
400
800
1200
1600
400
800
1200
1600
LA-3000
2000
2500
3000
3500
4000
IX-x
400
800
1200
1600
400
800
1200
1600
LA-4000
2000
2500
3000
3500
4000
X
400
800
1200
1600
400
800
1200
1600
Secondary
Pick-Up
Current-Arnperes
0.50
0.625
0.75
0.875
1.00
-
0.10
0.20
0.30
0.40
0.10
0.20
0.30
0.40