Testing First Generation Trip Devices
19
labeled “Instantaneous Trip Setting” (4). The Short Time Pick-
Up is labeled “Transfer to Short Time (5). There are no test
jacks provided on the front of the device. Connections for
trigger indication are made to points on the terminal block as
shown in Figures 9 through 12. (6) On STATIC TRIP II the knob
reference dots (knob counterclockwise against stop) are
black and the calibration dots are red. On first generation trip
devices the reference dots are red and the calibration dots
are black on some models and white on others.
NOTE
Once pickup has been verified, disconnect the indicators for
Time Delay Testing. The indicators can load the circuit and
prevent the trip device from timing out.
Test Procedures
Keeping the above differences in mind and making careful
reference to the appropriate connection diagram in Figure 9
through 12, the test instructions in “Testing Static Trip on the
Breaker” (omitting the connection instructions in each case),
can be used for testing first generation trip devices also.
Compare the test results with Table 3 and Figures 13, 14, 15,
16 and 17 as applicable.