The following components must be set prior installing the module in the enclosure:

Verify that the dedicated circuit breaker for the PSC-12 is turned OFF at the mains.

Battery Circuit Breaker

: Set this circuit breaker to the OFF position.

Network Address Switch

: Set the three-digit HNET network address for

the PSC-12 using the three rotary dial address switches located below the
LEDs on the front panel. (Refer to Figure 2 for the location of the switches.)
The address for the PSC-12 must be the same as the address selected for it
in the Zeus Programming Tool. To set the address, turn the pointers on each
of the three dials to the numbers for the selected address. For example, if
the address is 123, set the pointer for the HUNDREDS dial to “1”, set the
pointer for the TENS dial to “2”, and set the pointer for the ONES dial to “3”.
The range of allowable addresses is from 001 to 251 (leading zeros must be
used).

INSTALLATION

Remove all system power before installation, first battery then AC. (To power up,

connect the AC first, then the battery.)

The PSC-12 mounts on studs in the backbox or on the optional Mounting Plate
(CAB-MP). The Mounting Plate may be located either inside or outside of the enclo-
sure to perform this installation procedure. If the Mounting Plate is located inside the
enclosure you will have to gain access to it by opening the enclosure Inner and Outer
doors. If the Mounting Plate is located outside of the enclosure, place it in front of

you so that the word “TOP” is at the top and away
from you.

The PSC-12 can occupy any position in the backbox or
on the mounting plate, but it should be installed in the
row and position that is located directly above the PTB
to which it is connected. (Refer to Figures 5 and 7).
When the PSC-12 is mounted correctly on the optional
Mounting Plate it will be flush on the top, bottom, and
right with the Mounting Plate and the mounting screw
holes of the PSC-12 will align with the threaded posts.

1. Install four 10-32 screws in the threaded posts at

the mounting position. Screw each of the 10-32
screws into the threaded posts 5-6 turns.

2. Place the PSC-12 over the four screws on the

Mounting Plate and slide it down or towards you to
rest on the four screws. (Refer to Figure 6.) When
the PSC-12 is in the correct position it will be flush
with the top, bottom and right side of the Mounting
Plate.

3. Tighten the four screws.

Figure 5

Location Of The PSC-12 On The Optional CAB-MP

TOP

TOP THREADED POSTS

BOTTOM THREADED POSTS

POSITION 1

POSITION 3

POSITION 4

POSITION 2

POSITION 1

POSITION 3

POSITION 4

POSITION 2

CAB-MP

Summary of Contents for PSC-12

Page 1: ...on the battery input It provides connection to a tamper switch and terminal tie points for system signals The PSC 12 communi cates directly to the PMI PMI 2 PMI 3 XLS FCM2041 U2 Desigo Fire Safety Modular FCM2041 U3 Cerberus PRO Modular to report fault conditions and allows the PMI PMI 2 PMI 3 XLS FCM2041 U2 Desigo Fire Safety Modular FCM2041 U3 Cerberus PRO Modular to query the status of the powe...

Page 2: ...igo Fire Safety Modular FCM2041 U3 Cerberus PRO Modular to query the state of the power supply and its current load and can send a diagnostics command to the PSC 12 It also provides the control of the relays The degrade ALARM bus and degradeTROUBLE bus will override the command that is sent by the PMI PMI 2 PMI 3 XLS FCM2041 U2 Desigo Fire Safety Modular FCM2041 U3 Cerberus PRO Modular to the Alar...

Page 3: ... its outputs 24V 12A FAIL Yellow Normally OFF When illumi nated indicates that the 24VDC non power limited output has a trouble condition or the PSC 12 has disconnected the 24VDC output due to current overload or short circuit 24V 4A FAIL Yellow Normally OFF When illumi nated indicates that the 24VDC power limited output has a trouble condition or the PSC 12 has disconnected the 24VDC power output...

Page 4: ...mally connected to the modules and cards located on the door of the enclosure or to remote CAN network modules This output is power limited to NFPA 70 per 760 All wiring must be in accordance with Article 760 of NEC or local building codes See Figure 2 Output Voltage 24VDC 10 15 Output Current 4A max TB3 1 terminal TB3 2 terminal TB4 24VDC Non Power Limited OutputTerminal This terminal is non powe...

Page 5: ...wers the CC 5 CC 2 modules It also contains all the communication signals and system signal bus that is necessary for the proper operation of the system These connectors are power limited If the PSC 12 is located in a different row in the enclosure an optional extended ribbon cable Model BCL P N 599 633997 must be used Output Voltages 24VDC 6 2VDC Max Current 2A 24VDC 2A 6 2VDC PRE INSTALLATION Th...

Page 6: ...ocated either inside or outside of the enclo sure to perform this installation procedure If the Mounting Plate is located inside the enclosure you will have to gain access to it by opening the enclosure Inner and Outer doors If the Mounting Plate is located outside of the enclosure place it in front of you so that the word TOP is at the top and away from you The PSC 12 can occupy any position in t...

Page 7: ...ors at the top of the PSC 12 are power limited The terminals and connectors at the bottom of the PSC 12 are non power limited Refer to Figure 7 Use a separate or dedicated circuit breaker and run the earth ground from a suitable source to the PSC 12 Check local requirements Conduit is not an acceptable Earth Ground Conductor Figure 6 Mounting The PSC 12 On The Optional CAB MP TOP SLIDE DOWN UNTIL ...

Page 8: ... 3 batteries are required connect them to the system with the Battery Cable Conversion Kit P N 545 634222 following the steps listed below 1 Using the 12 in long wire assembly connect the two batteries together as shown in Figure 7 Secure each end of the assembly to the battery with a 10 32 x 3 4 screw and lock nut 2 Attach the quick disconnects to the positive and negative battery terminals with ...

Page 9: ...r Power Supply Load and Battery Calculations The PSC 12 power supply load and battery size calculations are performed by the Zeus tool based on the equipment in the physical view Once all of the equipment is inserted into the physical view for each enclosure and a successful compile is performed the results of the calculations are shown in the report view From theTools menu select Report Generatio...

Page 10: ...P N 500 633917 with the BTX 2 and BTX 3 models Battery System Electrical Rating Input Voltage 24VDC 10 15 Input Current 15A max Minimum Battery size 15AH Maximum Battery size 100AH Battery Max Charge Current 5A full charge mode ELECTRICAL RATINGS e g a t l o V t u p n I z H 0 6 0 5 C A V 0 2 1 z H 0 6 0 5 C A V 0 2 2 z H 0 6 0 5 C A V 0 4 2 t n e r r u C t u p n I C A V 0 2 1 x a M A 5 3 C A V 0 2...

Page 11: ... needs Such a security concept may result in additional site specific preventive action to ensure that the building comfort fire safety security management or physical security system for your site are operated in a secure manner These measures may include but are not limited to separating networks physically protecting system components user awareness programs defense in depth etc For additional ...

Page 12: ...Building Technologies Division Florham Park NJ Siemens Canada Ltd 1577 North Service Road East Oakville Ontario L6H 0H6 Canada P N 315 033060 19 Siemens Gebäudesicherheit GmbH Co oHG D 80930 München Document ID A6V10239105 ...

Reviews: