background image

Siemens Industry, Inc.
Building Technologies  Division

P/N 315-033060-19

3

The LEDs located at the top left of the module and are
defined as follows:

POWER -

(Green)

Normally ON. When illumi-

nated, indicates that the PSC-12 is
powered from the AC mains. When
flashing, indicates that the PSC-12 is
powered from the battery.

MODULE FAIL -

(Yellow)

Normally OFF. When illumi-

nated indicates that the module micropro-
cessor has failed.

CAN FAIL -

(Yellow)

Normally OFF. When illumi-

nated, indicates that CAN communica-
tion with the PSC-12 has terminated
(applicable only when PSC-12 resides in
a CAN network).

HNET FAIL -

(Yellow)

Normally OFF. When illumi-

nated, indicates that the HNET communi-
cation with the PSC-12 has terminated and
the PSC-12 goes to degrade mode
(applicable only when the card resides in
the HNET network).

GND FAULT -

(Yellow)

Normally OFF. When illumi-

nated, indicates that the PSC-12 has
detected either a negative or positive
ground fault on its outputs.

24V 12A FAIL -

(Yellow)

Normally OFF. When illumi-

nated, indicates that the 24VDC non-
power limited output has a trouble
condition or the PSC-12 has disconnected
the 24VDC output due to current overload
or short circuit.

24V 4A FAIL -

(Yellow)

Normally OFF. When illumi-

nated, indicates that the 24VDC power
limited output has a trouble condition or
the PSC-12 has disconnected the 24VDC
power output due to current overload or
short circuit.

Three rotary dial switches located directly below the LEDs are used to set the HNET/
CAN network address of the PSC-12.

The terminal blocks of the PSC-12 are defined as follows (See Figures 2, 3 and 4):

TB1

Terminals 1, 2 and 3 provide connection to the FMT riser.

Terminals 4, 5 and 6 provide an output to the monitor speaker in a
remotely mounted LVM.

Terminals 7, 8 and 9 provide an input from the microphone of a remotely
mounted LVM.

Figure 2

Terminal Blocks, Controls and Indicators

NOTE:
Positive and negative ground fault detected at:
<50K ohms for TB3 terminals 1,2
<60K ohms for TB4 terminals 1,2
<40K ohms for TB1 terminals 10,11
<20K ohms for TB1 terminals 4,5,7,8
<30K ohms for TB1 terminals 1,2

Summary of Contents for PSC-12

Page 1: ...on the battery input It provides connection to a tamper switch and terminal tie points for system signals The PSC 12 communi cates directly to the PMI PMI 2 PMI 3 XLS FCM2041 U2 Desigo Fire Safety Modular FCM2041 U3 Cerberus PRO Modular to report fault conditions and allows the PMI PMI 2 PMI 3 XLS FCM2041 U2 Desigo Fire Safety Modular FCM2041 U3 Cerberus PRO Modular to query the status of the powe...

Page 2: ...igo Fire Safety Modular FCM2041 U3 Cerberus PRO Modular to query the state of the power supply and its current load and can send a diagnostics command to the PSC 12 It also provides the control of the relays The degrade ALARM bus and degradeTROUBLE bus will override the command that is sent by the PMI PMI 2 PMI 3 XLS FCM2041 U2 Desigo Fire Safety Modular FCM2041 U3 Cerberus PRO Modular to the Alar...

Page 3: ... its outputs 24V 12A FAIL Yellow Normally OFF When illumi nated indicates that the 24VDC non power limited output has a trouble condition or the PSC 12 has disconnected the 24VDC output due to current overload or short circuit 24V 4A FAIL Yellow Normally OFF When illumi nated indicates that the 24VDC power limited output has a trouble condition or the PSC 12 has disconnected the 24VDC power output...

Page 4: ...mally connected to the modules and cards located on the door of the enclosure or to remote CAN network modules This output is power limited to NFPA 70 per 760 All wiring must be in accordance with Article 760 of NEC or local building codes See Figure 2 Output Voltage 24VDC 10 15 Output Current 4A max TB3 1 terminal TB3 2 terminal TB4 24VDC Non Power Limited OutputTerminal This terminal is non powe...

Page 5: ...wers the CC 5 CC 2 modules It also contains all the communication signals and system signal bus that is necessary for the proper operation of the system These connectors are power limited If the PSC 12 is located in a different row in the enclosure an optional extended ribbon cable Model BCL P N 599 633997 must be used Output Voltages 24VDC 6 2VDC Max Current 2A 24VDC 2A 6 2VDC PRE INSTALLATION Th...

Page 6: ...ocated either inside or outside of the enclo sure to perform this installation procedure If the Mounting Plate is located inside the enclosure you will have to gain access to it by opening the enclosure Inner and Outer doors If the Mounting Plate is located outside of the enclosure place it in front of you so that the word TOP is at the top and away from you The PSC 12 can occupy any position in t...

Page 7: ...ors at the top of the PSC 12 are power limited The terminals and connectors at the bottom of the PSC 12 are non power limited Refer to Figure 7 Use a separate or dedicated circuit breaker and run the earth ground from a suitable source to the PSC 12 Check local requirements Conduit is not an acceptable Earth Ground Conductor Figure 6 Mounting The PSC 12 On The Optional CAB MP TOP SLIDE DOWN UNTIL ...

Page 8: ... 3 batteries are required connect them to the system with the Battery Cable Conversion Kit P N 545 634222 following the steps listed below 1 Using the 12 in long wire assembly connect the two batteries together as shown in Figure 7 Secure each end of the assembly to the battery with a 10 32 x 3 4 screw and lock nut 2 Attach the quick disconnects to the positive and negative battery terminals with ...

Page 9: ...r Power Supply Load and Battery Calculations The PSC 12 power supply load and battery size calculations are performed by the Zeus tool based on the equipment in the physical view Once all of the equipment is inserted into the physical view for each enclosure and a successful compile is performed the results of the calculations are shown in the report view From theTools menu select Report Generatio...

Page 10: ...P N 500 633917 with the BTX 2 and BTX 3 models Battery System Electrical Rating Input Voltage 24VDC 10 15 Input Current 15A max Minimum Battery size 15AH Maximum Battery size 100AH Battery Max Charge Current 5A full charge mode ELECTRICAL RATINGS e g a t l o V t u p n I z H 0 6 0 5 C A V 0 2 1 z H 0 6 0 5 C A V 0 2 2 z H 0 6 0 5 C A V 0 4 2 t n e r r u C t u p n I C A V 0 2 1 x a M A 5 3 C A V 0 2...

Page 11: ... needs Such a security concept may result in additional site specific preventive action to ensure that the building comfort fire safety security management or physical security system for your site are operated in a secure manner These measures may include but are not limited to separating networks physically protecting system components user awareness programs defense in depth etc For additional ...

Page 12: ...Building Technologies Division Florham Park NJ Siemens Canada Ltd 1577 North Service Road East Oakville Ontario L6H 0H6 Canada P N 315 033060 19 Siemens Gebäudesicherheit GmbH Co oHG D 80930 München Document ID A6V10239105 ...