background image

  

Service Information 
Electrostatic Discharge 

  

18 
Siemens Industry, Inc. 

 

125-5065T 

 

 

2012-08-06 

 

 

Service Information 

This section describes corrective measures you can take if you encounter a problem 

with an MS/TP PPM device. If you encounter a symptom or a problem not covered in 

this manual, contact your Siemens Solution Partner, Authorized TALON Dealer

 

 

NOTE: 

When removing power to a controller to perform maintenance or service, make sure 

that the person in charge of the facility is aware of this and that appropriate steps are 

taken to keep the building in control. 

 

 

 

 

NOTE: 

When troubleshooting, record the problem and what actions were performed 

immediately before the problem occurred. Being able to describe the problem in detail 

is important should you need assistance from your local Siemens Solution Partner, 

Authorized TALON Dealer. 

 

To view the status of the MS/TP PPM device and to call up reports for troubleshooting, 

you can use an operator's terminal and the operator interface or a TALON View 

workstation. For more information, see the following documentation: 

  TALON Firmware User's Manual (588-580

It is good practice to back up the 

). 

MS/TP PPM

While performing the troubleshooting procedures outlined in this manual, you may 

want to refer to the 

 device database routinely and whenever 

changes are made to the database or new equipment is added. 

TALON Wiring Guidelines Manual (588-581

 

). 

Electrostatic Discharge 

An electrostatic discharge (ESD) wrist strap is generally not required when installing or 

servicing an MS/TP

 

 PPM. However, if the device is installed in a very dry environment 

where a high static discharge is likely, an ESD wrist strap is recommended. 

Ordering Replacement Parts 

If a MS/TP

 

 PPM is not operating correctly, it should be replaced. 

Reinstalling the Mounting Tabs 

Do the following to reinstall a DIN mounting tab: 
1.  Place the wire spring clip into the pocket in the channel for the mounting tab. 
2. 

 

Make sure the mounting tab is face down. Working from the center (inside) of the 

base, slide the mounting tab into the channel. (See the following figure.) 

  

  

  

  

Summary of Contents for PPM-1U32.BPF

Page 1: ...125 5065T Building Technologies 2012 08 06 MS TP Point Pickup Module Owner s Manual ...

Page 2: ...offices and authorized distributors offer Technical Support Programs that will ensure continuous trouble free system performance For further information contact your nearest Siemens Industry Inc representative Copyright 2012 by Siemens Industry Inc FCC Regulations The manual for an intentional or unintentional radiator shall caution the user that changes or modifications not expressly approved by ...

Page 3: ...t the dealer or an experienced radio TV technician for help Your feedback is important to us If you have comments about this manual please submit them to mailto Sbt_technical editor us sbt siemens com Credits Staefa and TALON are registered trademarks of Siemens Industry Inc Other product or company names mentioned herein may be the trademarks of their respective owners Printed in USA ...

Page 4: ......

Page 5: ...ported Sensor Types 9 Specifications 10 Communication RS 485 Port 11 HOA Hand Off Auto 12 DIP Switch Settings 13 Baud Rate Settings 13 Status LEDs 14 Change of Value Implementation 15 Accuracy Resolution 15 Wiring 16 I O Configuration Diagrams 17 Service Information 18 Electrostatic Discharge 18 Ordering Replacement Parts 18 Reinstalling the Mounting Tabs 18 Glossary 20 Index 21 ...

Page 6: ...the incorporation of a cluster of remote points into the Building Automation Station over the MS TP The PPM family leverages the MS TP network to extend the reach of any BTL listed BACnet Building Controllers application program network Each Universal Input can be configured for analog or digital input Input Output type is configured by writing to BACnet object properties MS TP Point Pickup Module...

Page 7: ...ue Siemens operator workstation Revision 3 11 and later provide System Profile icons representing MS TP PPM devices Siemens BACnet operator workstations with BOB BACnet Object Browser available with Rev 3 7 and later provide the ability to modify the MS TP PPM s custom default device ID device name and COV increment NOTE BACnet systems consist of devices that communicate using the BACnet protocol ...

Page 8: ...oard Diagrams 8 Siemens Industry Inc 125 5065T 2012 08 06 Board Diagrams Figure 1 6 Point Analog controller board Figure 2 6 Point Digital controller board Figure 3 12 Point Combination controller board ...

Page 9: ...Binary Inputs Status indication voltage free dry contact 4 2 5 Counter Count accumulator voltage free dry pulse contact 3 Analog inputs w 12 bit A D resolution Temperature Ni 1000 4 4 Temperature Pt 1000 385 4 4 Temperature NTC 10K Type II 1 Voltage DC 0 to 10V 4 4 Current DC 4 to 20 mA 2 Digital outputs BO OnOff NO Contact 240 Vac 5A Resistive 2 A General Purpose 2 3 Analog outputs DC 0 to 10V 2 ...

Page 10: ... or dry contact Digital Outputs 6 Point Digital PPMs PPM 1U32 BPR and PPM 1U32 BPF 2 Form A NO Normally Open Relays 24 to 240 Vac 5A resistive 2A General Purpose 5 2 2 Hand Off Auto switches provide manual operation of the relays for commissioning 6 Point Digital PPM PPM 1U32 BPR 12 Point Combination PPMs PPM 2U3322 BPFand PPM 2U3322 BPR 3 Form A NO Normally Open Relays 24 to 240 Vac 5A resistive ...

Page 11: ...50 C Humidity Range 5 to 95 rh non condensing Communication RS 485 Port The RS 485 port provides a path for commands and information transmitted between field panels or other BACnet devices This port provides communications over an RS 485 BACnet MS TP The RS 485 port provides half duplex asynchronous serial RS 485 communications over shielded twisted pair cable The communication terminations netwo...

Page 12: ...witches are available only for the Digital MS TP PPM PPM 1U32 BPR These switches can be used for commissioning In the H position the digital output is ON in the O position the digital output is OFF For system control the switch must be set to the A position Figure 4 Hand Off_Auto Switches Digital Only ...

Page 13: ...ches 1 through 8 are used to set the MAC address Switches 9 and 10 are used to set the communication speed baud rate Figure 5 DIP Switches Baud Rate Settings Use DIP Switches 9 and 10 to set the device s communication speed baud rate Baud Rate Switch 9 Switch 10 9600 OFF OFF 19200 OFF ON 38400 ON OFF 76800 ON ON ...

Page 14: ... Indication DO DO1 DO2 DO3 Indicates the ON OFF status of the associated DO A glowing LED indicates that the DO is energized The 6 point digital and 12 point combination controllers have two and three DOs respectively Power Receive POWER RX Indicates the power and communication status of the device Solid ON indicates device is powered no communication OFF indicates unit not powered Flashing indica...

Page 15: ...STP network and can be adjusted down for better resolution or up for less network traffic Default COV limit is 0 5 for AI s and AO s thermistor NTC10K Ni1000 Pt1000 0 5F 0 10V or 4 20 mA 1 MaxInfoFrames is configurable from 1 to 15 the default is 12 This variable specifies the maximum number of information frames COVs the node may send before it must pass the token Accuracy Resolution Signal Accur...

Page 16: ...emens Industry Inc 125 5065T 2012 08 06 Wiring See the Wiring Guidelines Manual 125 3002 for additional wiring information Figure 9 Power Wiring Figure 10 FLN 2 wire network interface Figure 11 FLN 3 wire interface ...

Page 17: ...stry Inc 125 5065T 2012 08 06 I O Configuration Diagrams Figure 12 AI DI wiring for 6 point digital Figure 13 DO wiring for wiring for 6 point digital Figure 14 Analog input wiring Figure 15 Universal input wiring Figure 16 Analog output wiring ...

Page 18: ...e an operator s terminal and the operator interface or a TALON View workstation For more information see the following documentation TALON Firmware User s Manual 588 580 It is good practice to back up the MS TP PPM While performing the troubleshooting procedures outlined in this manual you may want to refer to the device database routinely and whenever changes are made to the database or new equip...

Page 19: ...Service Information Reinstalling the Mounting Tabs 19 Siemens Industry Inc 125 5065T 2012 08 06 NOTE The end with the screw hole slides into the channel first Figure 17 Reinstalling a DIN Mounting Tab ...

Page 20: ... a two state signal such as ON OFF and OPEN CLOSE For example low temperature detectors differential pressure switches flow proof switches and door closures digital output DO point Point that sends a two state signal such as ON OFF and OPEN CLOSE For example two speed fan motor starters two position valves and dampers pump motor starters lighting switches and chiller and boiler switches HAND OFF A...

Page 21: ...d diagrams 8 wiring 16 17 DIP switch 13 E electrostatic discharge ESD 18 H Hand Off Auto switches 12 I I O configuration diagrams 17 N communication network 11 compatibility 7 wiring 16 O overview 6 S service information 18 electrostatic discharge ESD 18 reinstalling the mounting tabs 18 baud rate settings 13 DIP switch 13 Hand Off Auto 12 specifications 10 status LEDs 14 DIP switches 13 Hand Off ...

Page 22: ...hnologies Division 1000 Deerfield Pkwy Buffalo Grove IL 60089 Tel 1 847 215 1000 2012 Copyright Siemens Industry Inc Technical specifications and availability subject to change without notice Document ID 125 5065T 125 5065T AA Edition 2012 08 06 ...

Reviews: