Technical Instructions
Low Temperature Detection Cut-out and Alarm Thermostat
Document Number 155-016P25
Rev.1, February, 2000
Information in this publication is based on current specifications. The company reserves the right to make changes in specifications and models as
design improvements are introduced. Powers is a trademark of Siemens Building Technologies, Inc. © 2000 Siemens Building Technologies, Inc.
Siemens Building Technologies, Inc.
Landis & Staefa Division
1000 Deerfield Parkway
Buffalo Grove, IL 60089-4513
U.S.A.
Document No. 155-016P25
Printed in the U.S.A.
Page 6
Adjustment
After mounting the thermostat, adjust the temperature setting using the set point
adjusting screw on the top of the enclosure. See
Figure 4.
Observe a complete operating cycle to be sure that all components function correctly.
Figure 4. Set Point Adjustment Screw.
Calibration
There is no field calibration required for the thermostat.
Troubleshooting
Observe a complete operating cycle to be sure that all components function correctly.
Service
There is no servicing of the thermostat. Replace if inoperative.
Dimensions
Figure 5. Dimensions in Inches (Millimeters).