Appendix
Object list
10
A6V11471220_en--_e
59 | 70
providing the
remaining duration of
an activated temporary
HRV fan mode.
TmpFanModeRemain
Time will be zero if no
temporary HRV fan
mode is active or in
case of an activated
Kitchen Hood mode
which is not
automatically
terminated by timeout.
TempDHWEf
f
21
0
1
V16Z8 /
DPT_TempHV
ACAbs_Z
R
IR.in
d
TempDHWEff refers to
the process input
property of AB UHD to
indicate the effective
DHW temperature for
visualization purposes
on PL-Link Room
Units.
TempDHWEff is
calculated by the BA-
Device, e.g. an
average of
upper/lower DHW
sensors in the DHW
storage tank
TempDHWS
etpEff
21
1
1
V16Z8 /
DPT_TempHV
ACAbs_Z
R
IR.in
d
TempDHWSetpEff
refers to the process
input property of AB
UHD to indicate the
currently effective
DHW temperature
setpoint for
visualization purposes
on PL-Link Room
Units.
DHWModeEf
f
21
3
1
N8Z8
R
IR.in
d
DHWModeEff refers to
the process input
property of AB UHD to
indicate the currently
effective DHW
operating mode for
visualization.
DelayedHVA
CModeEff
17
1
1
N8
R
IR.in
d
DelayedHVACModeEff
refers to the
proprietary and
optional process input
property to indicate if a
manually triggered
room operating mode
is delayed by an
application specific
function (e.g.
unoccupied selection
and delayed HOME
(Comfort) -> AWAY
(Economy) transition).
DelayedHVACModeEff
is provided by ABI
RSMHD
TmpFanMod
eCountdown
21
6
1
DPT_State
R
IR.in
d
TmpFanModeCountdo
wn refers to the
optional and
proprietary process
input property of AB
UHD to differentiate