Power supply
Operating voltage
KNX PL-Link DC 21...30 V
Max power consumption
7...10 mA
Interfaces
Type of port between controller and room
operating unit KNX PL-Link
KNX PL-Link
Baud rate
9.6 kbps
Protocol
KNX PL-LINK
Standard KNX connector
Wire diameter 0.8 mm, max. 1.0 mm (solid conductors
only)
Cable type
2-core twisted pair, stranded, solid
Single cable length (from room automation
station to room operating unit)
<1000 m
Section
0.5…1.5 mm²
Bus line polarity
PL+, PL-
Bus terminating resister
not required
Sensor data
Temperature Sensor
Measuring element
NTC resistance sensor
Measuring range
0...50 °C
Measuring accuracy (5...30 °C)
±0.8 °C
Measuring accuracy (25 °C)
±0.5 °C
Humidity Sensor
(only for
POS8.4440/109)
Measuring range
10 %...95 % r.h.
Accuracy (r.h. 20 %...80 %)
±4 % at 25 °C
Accuracy (r.h. 0 %...20 %, 80 %...95 %)
±6 % at 25 °C
Ambient conditions and protection classification
Housing protection
Protection standard as per EN 60529
●
IP30
●
IP33 for surface part
Insulation protection class
Class III
Climatic ambient conditions
●
Normal operation
●
Transport
●
Environmental conditions: Class 3K5
Temperature 0...50 °C
Air humidity <85% r.h.
●
Environmental conditions: Class 2K3
Temperature -25...70 °C
Air humidity <95% r.h.
Mechanical ambient conditions
Normal operation
Transport
Class 3M2