7ML19985QJ83
Pointek CLS100 – QUICK START MANUAL
Page EN-15
Englis
h
Fully Synthetic Process Connection (Enclosure
Version)
Red and Yellow LEDs are
blinking fast
Proper power not applied
to device.
Power range must equal
12 to 33 V DC at all times
(10 to 30 V DC for IS
versions)
Check power source
Minimum 12 V DC on the terminals
when the signal current is 20 mA
(minimum 10 V DC for IS versions)
Red and Yellow LEDs are
blinking while switching
Proper power not applied
to device.
Power range must equal
12 to 33 V DC at all times
(10 to 30 V DC for IS
versions)
Check power source
Minimum 12 V DC on the terminals
when the signal current is 20 mA
(minimum 10 V DC for IS versions)
Solid state contact does
not follow status Red LED
Defective component in
device. Probable cause:
wrong wiring in this
circuit.
Contact distributor
Yellow LED is lit while
probe is not covered
May indicate significant
product buildup.
Rotate sensitivity potentiometer
further CCW (counter clockwise)
Check sensor tip
Symptom
Cause
Action
Green LED off
Proper power not
applied to device
Power range must equal
12 to 33 V DC at all times
(10 to 30 V DC for IS
versions)
Check power source
Minimum 12 V DC on the terminals
when the signal current is 20 mA
(minimum 10 V DC for IS versions)
Green LED off, with proper
supply
Defective component in
device.
Connector came loose
Contact distributor
Refasten connector
Green LED on and Yellow
LED on while not
responding to product
and/or adjustment
Proper power not
applied to device.
Power range must equal
12 to 33 V DC at all times
(10 to 30 V DC for IS
versions)
Check power source
Minimum 12 V DC on the terminals
when the signal current is 20 mA
(minimum 10 V DC for IS versions)
Hysteresis region too
great
Proper power not
applied to device
Power range must equal
12 to 33 V DC at all times
(10 to 30 V DC for IS
versions)
Check power source
Minimum 12 V DC on the terminals
when the signal current is 20 mA
(minimum 10 V DC for IS versions)