Pointek CLS100 – QUICK START MANUAL
Page EN-9
Englis
h
HIGH Alarm
4 / 20 mA Loop Alarm Application
Fully Synthetic Process Connection (Enclosure Version)
Stainless Steel Process Connection (Integral Cable or Enclosure Version)
Intrinsically Safe Version only
Solid State Switch Application
Solid state switch output
12-33 V DC (polarity determines operation)
+
-
Note: numbers refer to enclosure versions. See p. 7
V supply
12-33 V DC
For example, 250
:
gives 1 or 5 V DC switch
voltage to PLC.
Rmax = V supply – 12 V
20 mA
Note: numbers
refer to enclosure
versions. See p. 7
V supply
12-33 V DC
For example,
250
:
gives 1
or 5 V DC
switch voltage
to PLC.
Rmax = V supply – 12 V
20 mA
Note: numbers
refer to enclosure
versions. See p. 7
V supply
10-30 V DC
IS barrier required
IS barrier required
Solid state switch output
Note: numbers refer to
enclosure versions. See p. 7