background image

Figure 5

PLC-4 Wiring Diagram

P/N 315-093312-7

NO CONNECTIONS

STROBE POWER

SUPERVISION

CIRCUIT 3 IN

CIRCUIT 4 OUT

OMM

Terminal

Block

CIRCUIT 3 OUT

CIRCUIT 2 OUT

CIRCUIT 1 OUT

CIRCUIT 1 IN

Wiring shown for Circuit 1 is typical of circuits
used for audio.

Use the PL864-25A for 25V RMS circuits.
Use the PL864-70 for 70.7V RMS circuits.

Maximum wire size: 14 AWG twisted pair, unshielded
Minimum wire size:

18 AWG twisted pair, unshielded

Input/output ratings for each circuit:

Audio:

100W at 25V RMS
100W at 70.7V RMS

Strobe:

24 VDC at 4A (96W)

22

21

20

19

18

17

16

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

NO CONNECTIONS

CONNECT TO CLOSURE

MONITORING DEVICE

CONNECT TO CLOSURE

MONITORING DEVICE

AUDIO FROM AMP

AUDIO TO ASC-1 OR ASC-2

AMPLIFIER INPUT +

AUDIO FROM AMPLIFIER -

AUDIO TO ASC-1 OR ASC-2

AMPLIFIER INPUT -

CIRCUIT 2 IN

24 VOLTS +

TO ZC1-8B STROBE CARD INPUT

24 VOLTS -

FROM MMB, PSR-1 OR ANY UL LISTED POWER SUPPLY

MANUFACTURED BY ALARM-SAF, MODEL BN4-002-UL

24 VOLTS+

FROM MMB, PSR-1 OR ANY UL LISTED POWER SUPPLY

MANUFACTURED BY ALARM-SAF, MODEL BN4-002-UL

24 VOLTS -

TO ZC1-8B STROBE CARD INPUT

T

e

rm

in

a

ls1-8a

re

not

p

ower

limited.

T

e

rminals

15

-

2

2

a

re

power

limited.

Refer to Wiring Specification for MXL,
MXL-IQ and MXLV Systems,
P/N 315-092772 revision 6 or higher,
for additional wiring information.

CIRCUIT 4 IN

(Wiring shown for
Circuit 4 is typical
of circuits used for
strobes. Use the
PL864-25S plug-on
card only.)

Summary of Contents for PLC-4

Page 1: ...e PLC 4 the PL864 25A the PL864 70A the PL864 25S The PL864 25A and the PL864 70A plug onto the PLC 4 to limit power to audio circuits The PL864 25S plugs onto the PLC 4 to limit power to strobe circuits NOTE Use the PL 864S for strobe circuits only Using the PL 864S for audio circuits may damage the system Use the PL864 70A for 70 7V audio circuits only The PLC 4 plugs onto one of the OMM card ed...

Page 2: ...to either the CSM 4 or MMB b Determine which circuits will be used Refer to Figure 1 for the location of the circuits on the PLC 4 board and to Figure 5 for circuit wiring c Remove the PLC 4 card from its protec tive bag d Remove the PL864 25A PL864 25S or PL864 70A cards from their protective bags e Place the PL864 plug on cards one at a time over the connectors on the PLC 4 card for the desired ...

Page 3: ...s kept at right angles to the OMM board Otherwise the plug in card can damage or displace other components Wiring Refer to Figure 5 All wiring must comply with national and local codes Dress the leads properly Maintain the proper routing and distances between the wiring that is power limited terminals 15 22 and wiring that is not power limited terminals 1 8 Refer to the MME 3 or MLE 6 Power Limite...

Page 4: ...TIONS CONNECT TO CLOSURE MONITORING DEVICE CONNECT TO CLOSURE MONITORING DEVICE AUDIO FROM AMPLIFIER AUDIO TO ASC 1 OR ASC 2 AMPLIFIER INPUT AUDIO FROM AMPLIFIER AUDIO TO ASC 1 OR ASC 2 AMPLIFIER INPUT CIRCUIT 2 IN 24 VOLTS TO ZC1 8B STROBE CARD INPUT 24 VOLTS FROM MMB PSR 1 OR ANY UL LISTED POWER SUPPLY MANUFACTURED BY ALARM SAF MODEL BN4 002 UL 24 VOLTS FROM MMB PSR 1 OR ANY UL LISTED POWER SUPP...

Reviews: