Model PAD-5-CLSA
1
Technical Data
19
Siemens Industry, Inc.
A6V101030359_en--_c
Building Technologies Division
4.5 Technical Data
Supply input
Operating voltage
DC 26 V nominal, filtered
DC 3.3V nominal, filtered
Operating current (standby)
55mA
Max. operating current.
6.0 A
NAC circuit
Plug strip
X300, X400
Voltage
DC 24 V
Special Application for strobe loads
Regulated for non-pulsing loads
Standby operating current
Max. 10 mA
Active operating current
3 A (for a class A circuit or per class B
circuit)
Regulated current rating
0.3 A
Releasing circuit
Voltage
DC 24 V
Active operating current
3 A (for a class A circuit or per class B
circuit)
NAC circuit configured
as a Input Shorting
Device
Voltage
DC 24V
Current
< 10 mA
Line Impedance
Max. circuit resistance
1.6 Ω @ 3.0 A
Supervised for
Open circuit
Short circuit
Ground fault
Design
Short-circuit protection
Voltage surge protection
Power limited
AUX output
X300, X400
Voltage
DC 24 V
Special Application
Active operating Current
3A
Cable types
All (twisted recommended)
For detailed specifications refer to the
following documents:
A6V10315013 for Desigo
A6V10333396 for Cerberus PRO