Model PAD-5-CLSA
1
15
Siemens Industry, Inc.
A6V101030359_en--_c
Building Technologies Division
4.1 Wiring Class B Releasing
x
x
x
x
x
x
.
x
.
x
REL-EOL
SOLENOID
x
x
x
x
x
x
.
x
.
x
REL-EOL
SOLENOID
5_
+
5_
-
6_
+
6
_-
Polarity shown in ACTIVE mode
Figure 7: Wiring Class B Releasing
4.2 Wiring Class A Releasing
5_
+
5_
-
6_
+
6_
-
REL-EOL
SOLENOID
.
x
.
x
*SEE NOTE 1
*SEE NOTE 2
NOTE 1: LOOP WIRES SHOULD BE TERMINATED
DIRECTLY ONTO THE REL-EOL.
NOTE 2: LOOP WIRES SHOULD BE TERMINATED
DIRECTLY AT THE SOLENOID.
Polarity shown in ACTIVE mode
REL-EOL: Terminating resistor 24kΩ and diode (Siemens P/N 500-696359)
Maximum length of line of the relay connections is limited to a resistance of 3.5Ω
Figure 8: Wiring Class A Releasing