background image

3 / 10

A6V10636202_enAP_c

Siemens

2018-01-25

Building Technologies

Actuator motor / Gears

Brushless, robust DC motors ensure reliable operation regardless of load. The damper
actuators do not require an end position switch, are overload proof, and remain in place

upon reaching the end stop.

The gears are maintenance free and low noise.

Type summary

Type

Stock no.

Control

Operating

voltage

Positioning

signal Y

Position

indicator U =

DC 0…10 V

Feedback

potentio-

meter 5 kΩ

Self-adaption

of rotational

angle range

Aux.

switches

Rotary

direction

switch

GLB141.1E S55499-D385

Open-

close

or

three-

position

AC 24 V ~ /

DC 24…48 V

yes

GLB142.1E S55499-D386

yes

GLB146.1E S55499-D387

2

GLB341.1E S55499-D388

AC 100…240 V ~

GLB346.1E S55499-D389

2

GLB161.1E S55499-D398

Modu-

lating

AC 24 V ~ /

DC 24…48 V

DC 0/2...10 V

yes

yes

yes

GLB163.1E S55499-D399

DC 0...35 V

yes

yes

GLB164.1E S55499-D400

DC 0...35 V

yes

yes

2

GLB166.1E S55499-D401

DC 0/2...10 V

yes

yes

GLB361.1E S55499-D390

AC 100…240 V ~ DC 0/2...10 V

yes

yes

Nominal torque: 10 Nm (applies to all GLB..1E actuators)

Accessories

See data sheet N4698

Product documentation

Topic

Title

Document ID

Data sheet

Air damper actuators

A6V10636202_enAP_c

Technical basics

Rotary damper actuators without spring return GL..E

A6V10636196_en--_a

Mounting instructions

GDB..1E, GLB..1E

A6V10636143_----_a

Related documents such as environmental declarations, CE declarations, etc., can be down-

loaded at the following Internet address:

http://siemens.com/bt/download

Notes

Safety

Caution

National safety regulations

Failure to comply with national safety regulations may result in personal injury and property
damage.

Observe national provisions and comply with the appropriate safety regulations.

Use only properly trained technicians for mounting, commissioning, and servicing.

Summary of Contents for OpenAir GLB 1E Series

Page 1: ... Nm Operating voltage AC 24 V DC 24 48 V or AC 100 240 V Mechanically adjustable span between 0 90 Pre wired with 0 9 m long connection cables Type specific variations with adjustable offset and span for the positioning signal Position indication mechanical and electrical Feedback potentiometer Self adaption of rotational angle range and adjustable auxiliary switches for supplementary functions 30...

Page 2: ...in the achieved position if the control signal is maintained at a constant value for loss of operating voltage Position indication Mechanical Rotary angle position indication by using a position indicator Position indication Electrical The feedback potentiometer can be connected to external voltage to indicate the position Output voltage U DC 0 10 V is generated proportional to the rotary angle U ...

Page 3: ...2 10 V yes yes yes GLB163 1E S55499 D399 DC 0 35 V yes yes GLB164 1E S55499 D400 DC 0 35 V yes yes 2 GLB166 1E S55499 D401 DC 0 2 10 V yes yes GLB361 1E S55499 D390 AC 100 240 V DC 0 2 10 V yes yes Nominal torque 10 Nm applies to all GLB 1E actuators Accessories See data sheet N4698 Product documentation Topic Title Document ID Data sheet Air damper actuators A6V10636202_enAP_c Technical basics Ro...

Page 4: ...annels provided for this purpose Comply with all local and currently applicable laws and regulations Technical data Power supply GLB1 1E Operating voltage SELV PELV Frequency AC 24 V 20 19 2 28 8 V 50 60 Hz DC 24 48 V 20 19 2 57 6 V 1 Power consumption running GLB14 1E GLB16 1E 2 2 VA 1 3 W 2 5 VA 1 5 W Power consumption holding GLB14 1E GLB16 1E 0 5 W 0 7 W Power supply GLB3 1E Operating voltage ...

Page 5: ...utput voltage U Max output current wires 9 2 U G0 wires 9 2 U G DC 0 10 V DC 1 mA Protected against faulty wiring max AC 24 V DC 24 48 V Aux power supply G G GLB36 DC 24 V 20 max 10 mA Feedback potentiometer for GLB142 1E Change of resistance wires P1 P2 0 5000 W Load Max sliding contact current Permissible voltage at potentiometer SELV PELV Insulation resistance between potentiometer and housing ...

Page 6: ...netic compatibility Applications For use in residential commercial light industrial and industrial environments EU Conformity CE A5W00000176 2 RCM Conformity A5W00000177 2 EAC Conformity Eurasian conformity UL UL as per UL 60730 http ul com database cUL as per CSA C22 2 No 24 93 Environmental compatibility The product environmental declaration A5W00026066 2 contains data on environmentally compati...

Page 7: ... AC 100 240 V GLB16 1E modulating Y DC 0 2 10 V GLB16 1E modulating Y DC 0 35 V GLB361 1E modulating control AC 24 V DC 24 48 V AC 24 V DC 24 48 V AC 100 240 V Connection diagrams GLB1 1E AC 24 V DC 24 48 V Open close single wire control Single Pole Single Throw SPST Open close two wire control Single Pole Double Throw SPDT Three position control Modulating control ...

Page 8: ... G Y U 3 4 6 7 1 2 8 9 brown light blue black white red black grey pink BR BU BK WH RD BK GY PK Line AC 100 240 V Neutral conductor Positioning signal AC 100 240 V clockwise GLB34 1E Pos signal AC 100 240 V counter clockwise GLB34 1E System potential DC 24 V aux power supply GLB361 1E System neutral aux power supply GLB361 1E Signal in GLB361 1E Signal out GLB361 1E Feedback potentiometer a b c P1...

Page 9: ...ies Dimensions 68 2 7 min min 60 min 6 4634M01 max 95 50 4 5 x Dimensions in mm Revision numbers Type Valid from rev no Type Valid from rev no GLB141 1E C GLB164 1E A GLB142 1E C GLB166 1E C GLB146 1E C GLB361 1E C GLB161 1E C GLB341 1E C GLB163 1E A GLB346 1E C ...

Page 10: ...national Headquarters Gubelstrasse 22 6301 Zug Switzerland Tel 41 41 724 24 24 www siemens com buildingtechnologies Siemens Switzerland Ltd 2016 2018 Technical specifications and availability subject to change without notice Document ID A6V10636202_enAP_c Issue 2018 01 25 ...