background image

Document No. 129-367 

Installation Instructions  

September 1, 2003 

 

 

 

Table 1.  3-position Control 24 Vac. 

Color 

Standard

Symbol 

Function 

Terminal  

Designation 

Standard

Plenum

1 Supply 

(SP) 

G  Red  Red 

Control signal clockwise 

Y1 

Violet 

Violet 

7 Control 

signal 

counterclockwise 

Y2 Orange 

Orange 

Factory installed options 

S1 

Switch A  Common 

Q11 

Gray/red 

Black 

S2 

Switch A  N.C. 

Q12 

Gray/blue  Black 

S3 

Switch A  N.O. 

Q14 

Gray/pink  Black 

S4 

Switch B  Common 

Q21 

Black/red  Black 

S5 

Switch B  N.C. 

Q22 

Black/blue  Black 

S6 

Switch B  N.O. 

Q24 

Black/pink  Black 

P1 Feedback 

Potentiometer

0 to 100% P1 - P2 

a White/red 

Black 

P2 Feedback 

Potentiometer 

Common 

b White/blue Black 

P3 Feedback 

Potentiometer

100 to 0% P3 - P2 

c White/pink 

Black 

GDE/GLB13x, Continued 

24 Vac power supply 3-position control. 
 
Each wire has the standard symbol printed 
on it. See Table 1. 

M

A

B

1000

P1

P3

P2

S1

S4

S2 S3

S5 S6

1

6

7

EA0282R1

 

EA0635R2

24
Vac

EARTH GROUND

ISOLATING CLASS 2

TRANSFORMER FOR

24 Vac POWER

   :  SAFETY ISOLATING

TRANSFORMER

PER EN 60742

120 Vac

7 (ORANGE)

6 (VIOLET)

1 (RED)

NEUT

 

Figure 14.  3-position Control.

 

 

 

 

 

 

 

GDE/GLB16x 

24 Vac power supply 0 to 10V modulating 
control 

Each wire has the standard symbol printed 
on it. See Table 2. 

M

A

B

S1

S4

S2 S3

S5 S6

1

8

2

9

EA0284R1

 

Figure 15.  0 to 10V Modulating Control. 

 

Table 2.  Modulating Control. 

Standard 

Symbol 

Function 

Terminal 

Designation 

Color

 

1 Supply 

(SP) 

G  Red 

2 Neutral 

(SN) 

G0 Black 

0 to 10V input signal 

Gray 

Output for 0 to 10 Vdc 
position indication 

U Pink 

Factory installed options 

S1 

Switch A – Common 

Q11 

Black 

S2 

Switch A – N.C. 

Q12 

Black 

S3 

Switch A – N.O. 

Q14 

Black 

S4 

Switch B – Common 

Q21 

Black 

S5 

Switch B – N.C. 

Q22 

Black 

S6 

Switch B – N.O. 

Q24 

Black 

 

 

Siemens Building Technologies, Inc.  

Page 5 of 6

  

 

Summary of Contents for OpenAir GDE131.1P

Page 1: ...you do not follow a procedure as specified CAUTION Equipment damage or loss of data may occur if you do not follow a procedure as specified Instructions WARNING Do not open the actuator NOTE Place the actuator on the damper shaft so that the front of the actuator is accessible The label is on the front side 1 Determine whether the damper blades will rotate clockwise or counterclockwise to open See...

Page 2: ...nstalled 1 2 inch guide See Figure 3 EA0999R1 Figure 3 Removing 1 2 inch Ø shaft guide for 3 8 in or 5 8 in shaft 45 90 90 EA0679R3 f Mounting GDE GLB on 3 8 inch 8 10 mm shafts Figure 4 3 8 Ø inch shaft see Figure 1 Item f 1 A 3 8 inch shaft adapter is provided in actuator package 2 Hold the shaft insert so that the raised tabs are inserted last when placing the insert into the back of the actuat...

Page 3: ... of the points to the setting Manually turn the red ring of the B switch The narrower tab on the ring points to the setting See Figure 10 The auxiliary switch setting shafts rotate with the actuator NOTE The scale is valid only when the actuator is in the 0 position on clockwise motion 80 70 60 20 10 AUX SWITCH ADJUSTMENT A B 50 EA0636R2 Figure 10 Auxiliary Switch Setting Dial Mechanical Range Adj...

Page 4: ...iring must conform to NEC and local codes and regulations Use earth ground isolating step down Class 2 transformers Do not use autotransformers Determine the supply transformer rating by summing total VA of all actuators used It is recommended that one transformer power no more than 10 actuators WARNING Installations requiring Conformance All wiring for CE rated actuators must only be separated ex...

Page 5: ...position control Each wire has the standard symbol printed on it See Table 1 M A B 1000 P1 P3 P2 S1 S4 S2 S3 S5 S6 1 6 7 EA0282R1 EA0635R2 24 Vac EARTH GROUND ISOLATING CLASS 2 TRANSFORMER FOR 24 Vac POWER SAFETY ISOLATING TRANSFORMER PER EN 60742 120 Vac 7 ORANGE 6 VIOLET 1 RED NEUT Figure 14 3 position Control GDE GLB16x 24 Vac power supply 0 to 10V modulating control Each wire has the standard ...

Page 6: ...88P25 OpenAir Electronic Damper Actuators GDE GLB Series Non spring Return Rotary 24 Vac Three Position Control Information in this publication is based on current specifications The company reserves the right to make changes in specifications and models as design improvements are introduced OpenAir is a trademark of Siemens Building Technologies Inc Other product or company names mentioned herein...

Reviews: