VAV compact controller KNX / PL-Link GDB181.1E/KN and GLB181.1E/KN

CE1N3547en

Building Technologies

2016-01-29

Application

VAV compact controllers are primarily used for controlling a variable or constant air
volume flow.
System environments:

  Building automation systems using the Siemens peripheral bus PL-Link

(Desigo Total Room Automation)

  Building automation systems using KNX LTE-mode

(Synco 700 Step 3 and newer)

  Building automation systems using KNX S-mode (third-party integration and

freely programmable devices)

Application fields:

  Supply air control
  Extract air control
  Supply/extract cascade control with

  Ratio control 1:1
  Ratio control (positive/negative pressure)
  Differential control (positive/negative pressure)

  Air dampers with a nominal torque of up to 5 or 10 Nm

VAV compact controllers are not suitable for environments where the air is
saturated with sticky or fatty particles or contain aggressive substances.

Type summary

Type

Torque

Application range

Operating voltage

GDB181.1E/KN

5 Nm

0...300 Pa

AC 24 V

GLB181.1E/KN

10 Nm

0...300 Pa

AC 24 V

Please refer to data sheet N4698 for information on accessories and spare parts.

Equipment combinations

VAV compact controllers are KNX certified and may be connected to all KNX
devices compatible with S-mode data points.

Device

Type

Data sheet

Controllers and room units

Room thermostat with controller

RDG400KN

3192

Room thermostat

RDU341

3172

Universal controller

RMU7..

3144

Web server

OZW7..

5702

PL-Link automation station

PXC3..

9203

Tools for configuration and service

Handheld tool

AST10*

5851

Interface converter

AST11

5852

PC software for service

ACS941 v3.0 or later*  5854

Service kit ( AST11)

AST21

-

Tools for engineering and commissioning

(partially suitable for device configuration)

Tools for PL-Link

Desigo ABT / SSA

Tool for KNX LTE-mode

Synco ACS790

Tools for KNX S-mode

ETS3 / ETS4

*  AST 10 / ACS941 v2.x: limited functionality for VAV compact controllers

Summary of Contents for OpenAir E Series

Page 1: ...gitally configurable air volume controller Operating voltage AC 24 V Nominal torque 5 or 10 Nm air damper angular rotation can be adjusted mechanically from 0 to 90 Can be configured as a stand alone device per room or cascade control 1 1 pressure ratios positive or negative pressure Pre wired with a 0 9 meter power cable and 0 9 meter KNX cable Please refer to Technical Basics P3547 for a compreh...

Page 2: ...urated with sticky or fatty particles or contain aggressive substances Type summary Type Torque Application range Operating voltage GDB181 1E KN 5 Nm 0 300 Pa AC 24 V GLB181 1E KN 10 Nm 0 300 Pa AC 24 V Please refer to data sheet N4698 for information on accessories and spare parts Equipment combinations VAV compact controllers are KNX certified and may be connected to all KNX devices compatible w...

Page 3: ...e check screw The HMI consists of an LED 1 and a push button 2 LED display Description off dark a Device not connected to power source b Device is connected to power source and operates without failure orange flashing 1x Feedback for middle key press orange flashing Wait connection test or reset to factory settings red Connection test not successful red Device in programming mode green Connection ...

Page 4: ...sioning Parameter Setting Description Siemens factory setting n V 1 3 16 Characteristic value for the air volume flow set by the manufacturer OEM 1 max V 20 120 Maximum air volume flow 100 min V 20 100 Minimum air volume flow 0 Dir r or L Air damper rotation opening direction r Clockwise CW L Counter clockwise CCW r ADP Off or on Standard mode for air damper position display Mapping 0 90 0 100 Ada...

Page 5: ...ling Power supply and bus cabling must be tested After power up the device can assume the following states State desired behavior User action Device response LED Functionality available in all system environments Power up device starts up Connect device to power supply LED is orange goes off after power up is completed Faultless operation none LED is off Set device to programming addressing mode S...

Page 6: ...hines red b In ACS790 click button Programming mode Address assignment enter physical address click Write or a Select a VAV compact controller from the device list by ID IDs are collected during mounting b Double click the selected row to open the dialog box Address assignment Enter a physical address and short description for the selected VAV compact controller Click Write to close dialog box Rep...

Page 7: ...ion cable Cable length 0 9 m Number of cores and cross sectional area 2 x 0 75 mm 2 Degree of protection and safety class Degree of protection acc to EN 60529 Refer to mounting instruction IP54 Safety class acc to EN 60730 III Environmental conditions Operation transport IEC 721 3 3 IEC 721 3 2 Temperature 0 50 C 25 70 C Humidity non condensing 95 r h 95 r h Standards and Regulations Product safet...

Page 8: ...he product environmental declaration contains data on environmentally compatible product design and assessments RoHS compliance materials composition packaging environmental benefit disposal Internal diagrams The VAV compact controller is supplied with two prewired connecting and communication cables All interconnected devices must be connected to the same G0 p G CE CE 1 1 2 G0 2 3547G01 Tool Tool...

Page 9: ...th twin terminals or internally connected terminals may be encountered as well as bus connection in junction boxes Please refer to the technical basic documentation for product specific information The operating voltage at terminals G and G0 must comply with the requirements under SELV or PELV Safety transformers with twofold insulation as per EN 61558 required they must be designed to be on 100 o...

Page 10: ...logies 2016 01 29 Issued by Siemens Switzerland Ltd Building Technologies Division International Headquarters Gubelstrasse 22 6301 Zug Switzerland Tel 41 41 724 24 24 www siemens com buildingtechnologies Siemens Switzerland Ltd 2011 Technical specifications and availability subject to change without notice ...

Reviews: