SIMOVERT MASTERDRIVES

Pannello di servizio OP1S
Operator Panel OP1S

Istruzioni di servizio

Operating Instructions

Edizione / Edition: AA

477 459 4070 72 J AA-6R

Summary of Contents for OP1S

Page 1: ...SIMOVERT MASTERDRIVES Pannello di servizio OP1S Operator Panel OP1S Istruzioni di servizio Operating Instructions Edizione Edition AA 477 459 4070 72 J AA 6R ...

Page 2: ...zioni sono contenute nelle edizioni successive Per ogni consiglio di miglioramento siamo grati The reproduction transmission or use of this document or its contents is not permitted without express written authority Offenders will be liable for damages All rights including rights created by patent grant or registration of a utility model or design are reserved We have checked the contents of this ...

Page 3: ...elta menu 14 4 9 Visualizzazione parametri e variazione parametri 15 4 10 Segnalazioni di guasto e di allarme 20 4 11 Impostazione comandi mediante OP1S 21 4 Funzionamento bus 22 4 1 Configurazione slave 22 4 2 Cambio slave 23 5 Dati tecnici 24 AVVISO Queste istruzioni di servizio valgono solo per l OP1S in collegamento con apparecchi MASTERDRIVES ed una scheda di regolazione CUVC CUMC o MASTERDRI...

Page 4: ......

Page 5: ...ne per mezzo di un interfaccia seriale RS485 con protocollo USS Nella comunicazione l OP1S assume la funzione di Master Gli apparecchi collegati funzionano come Slaves L OP1S può funzionare con Baudrate di 9 6 kBd e 19 2 kBd Esso è in grado di comunicare con max 32 Slaves indirizzi da 0 a 31 Il pannello di servizio può essere perciò utilizzato sia in un accoppiamento punto a punto p e parametrizza...

Page 6: ... segni tasto segno tasto reset tasti cifre da 0 a 9 Jog 7 8 9 P Reset 0 4 5 6 1 2 3 O I Fault Run connettore allacciamento 9 poli SUB D lato posteriore apparecchio LED verde LED rosso Figura 1 1 Vista OP1S Allacciamento OP1S Pin Sigla Significato Campo 3 RS485 P Dati attraverso interfaccia RS485 5 M5V Massa 6 P5V Alimentazione ausiliaria 5 V 5 200 mA 8 RS485 N Dati attraverso interfaccia RS485 9 P...

Page 7: ...lo sportello dell armadio mediante adattatore Inserimento diretto sull apparecchio come p e appaecchi compatti MASTERDRIVE o unità di alimentazione MASTERDRIVE Kompakt PLUS Allacciamento con cavo S IE ME NS A S1 B X101 C X103 P USS Bus 7 4FSWJ JP Jog 7 8 9 P Reset 0 4 5 6 1 2 3 O I Fault Run OP1S U S S a t t r a v e r s o R S 4 8 5 5 4 3 2 1 9 8 7 6 5 4 3 2 1 9 8 7 6 lato OP1S presa 9 pol SUB D la...

Page 8: ...r active SIEMENS A S1 B X101 C X103 CM EE WR bus USS su X100 OP1S montato su unità di alimentazione SIEMENS A S1 B X101 C X103 WR SIEMENS A S1 B X101 C X103 SIEMENS A S1 B X101 C X103 WR WR Figura 2 2 OP1S per funzionamento bus con apparecchi Kompakt PLUS NOTA L unità di alimentazione Kompakt PLUS serve nel funzionamento su bus solo per il fissaggio meccanico di OP1S e per il traserimento del bus ...

Page 9: ...zo del pannello di servizio intergrato nell apparecchio con l OPS1 si può avviare senza ulteriori preparativi un accoppiamento punto a punto Alla messa in servizio di un sistema bus con l OP1S gli slaves devono dapprima essere configurati singolarmente staccando per questo le spine del cavo di bus ved par funzionamento bus Durante la fase di avviamento nella prima riga del Display viene dapprima s...

Page 10: ...legato viene riconfigurato cioè i parametri d interfaccia vengono impostati ai valori standard Numero PKW 127 Numero PZD 2 opp 4 Tempo caduta messaggio 0 ms Se nonostante ciò non si riesce a comunicare con lo slave le cause possono essere le seguenti cablaggio errato funzionamento bus con due o più slaves con uguale indirizzo di bus ved par Funzionamento bus la Baudrate impostata nello slave non è...

Page 11: ...ne Tasto commutazione Scelta del livello di menu e commutazione tra numero parametro indice parametro e valore parametro nella sequenza indicata Il livello attivo viene segnalato dalla posizione del cursore sul Display LC Il comando diventa attivo rilasciando il tasto Conclusione di una immissione numerica Reset Tasto Reset Abbandono di livelli menu Con segnalazione di guasto attiva tacitazione de...

Page 12: ...to numero slave 1 a riga a destra possono essere impostati mediante parametrizzazione 1 a riga a sinistra nell esempio corrente di uscita 1 a riga a destra nell esempio tensione impressa 2 a riga valore reale nell esempio valore reale velocità solo parametro di osservazione 3 a riga riferimento nell esempio riferimento velocità 4 a riga nell esempio condizione di funzionamento Nella segnalazione d...

Page 13: ...lave identificazione slave Poichè non tutte le righe possono essere visualizzate in una volta è possibile far scorrere la visualizzazione con i tasti diminuisci opp aumenta Ê Ê Ì Ì Ê Ê Ì Ì Ê Ê Ì Ì Ê Ê Ì Ì MotionControl scelta menu OP Upread OP Download MotionControl scelta menu OP Upread OP Download MotionControl scelta menu OP Upread OP Download MotionControl OP Upread OP Download canc dati Motio...

Page 14: ...ci opp aumenta viene selezionata la funzione identificazione slave e con P viene attivata Poichè non tutte le righe possono essere segnalate in una volta sola è possibile con diminuisci opp aumenta far scorrere la visualizzazione Inoltre in alto a destra viene segnalato il numero di slave Ê Ê P Ì Ì Ê Ê Ì Ì Ê Ê Ì Ì Ê Ê Ì Ì MotionControl cambio slave config slave ident slave MotionControl 00 Identif...

Page 15: ...read Pxxx Esempio selezione e avviamento del processo di Upread Con Reset il processo può essere interrotto in qualsiasi momento Se l Upread è stato eseguito completamente all utente è richiesto di immettere un identificativo di max 12 caratteriti per la serie parametri memorizzata Questo identificativo può p e essere costituito dalla data e e da altri caratteri di distinzione L immissione avviene...

Page 16: ...e avviato il processo di Download Durante il processo di Download l OP1S segnala il parametro corrente scritto Ê Ê P Ì Ì Ê Ê P Ì Ì Download 1909199701 MASTERDRIVES MC PLUS Download 1909199701 MASTERDRIVES MC PLUS MotionControl 00 Download Pxxx Esempio di conferma dell identificativo e avviamento del processo Download Con Reset il processo può essere interrotto in qualsiasi momento Se Download è st...

Page 17: ...ne attivata Ê Ê P Ì Ì MotionControl OP Upread OP Download canc dati Canc dati 1909199701 MASTERDRIVES MC PLUS Esempio di scelta e attivazione della funzione cancella dati Ora con diminuisci oppure aumenta si deve scegliere tra una delle serie di parametri memorizzate nell OP1S visualizzazione nella seconda riga Con P viene confermato l identificativo scelto Ora l identificativo di slave può essere...

Page 18: ...gue ancora un livello di sottomenu Scegliendo Menu parametri è possibile l accesso a tutti i parametri per mezzo di sottomenu opportunamente strutturati Scegliendo UpR accesso libero si accede direttamente al livello parametri 7x Ê Ê P Ì Ì Ê Ê Ì Ì Ê Ê Ì Ì MotionControl scelta menu OP Upread OP Download scelta menu parr utente menu parametri Impp fissa scelta menu imp azionam Download UpR accesso l...

Page 19: ...mero di parametro mediante tastiera numerica Ê Ê Ì Ì Ê Ê Ì Ì Ê Ê Ì Ì r001 9 cond convertitor pronto ins r002 0 min 1 velocità reale r004 0 0 A corrente uscita r006 0 V tensione impressa esempio di variazione del numero di parametro mediante aumenta Se il parametro all immissione delle cifre non esiste si ha la segnalazione PNU non esistente Scegliendo con aumenta opp diminuisci un numero di parame...

Page 20: ...testo di scelta 1 a riga numero parametro indice parametro valore parametro 2 a riga nome parametro 3 a riga testo indice 4 a riga testo di scelta P053 0006Hex abil param 0000000000000110 ComBoard no Esempio parametro senza indice con testo di scelta valore binario 1 a riga numero parametro valore parametro in Hex 2 a riga nome parametro 3 a riga valore parametro binario 4 a riga testo di scelta ...

Page 21: ...ametro avviene sempre e soltanto premendo il tasto P Il livello di volta in volta scelto numero parametro indice parametro valore parametro viene contraddistinto con il cursore In caso di immissione errata di un valore parametro con Reset si torna di nuovo al vecchio valore Con Reset si può anche saltare ad un livello inferiore Valore parametro Reset indice parametro Reset Nr par Parametri variabi...

Page 22: ...parametro Variazione valore parametro Accettazione e indietro Ê Ê P Ì Ì Ê Ê 5 Ì Ì Ê Ê P Ì Ì P600 0 ms tempo risp HS P600 0 ms tempo risp HS P600 5 ms tempo risp HS P600 5 ms tempo risp HS Scelta valore parametro Variazione valore parametro Ê Ê P Ì Ì Ê Ê Ì Ì Ê Ê P049 001 4 vis funz OP 1a riga sinistra P049 001 4 vis funz OP 1a riga sinistra P049 002 6 vis funz OP 1a riga destra Scelta valore parame...

Page 23: ...esto caso la parametrizzazione avviene mediante diversi sottomenu Esempio di questo procedimento con reset parametri 2x Ê Ê Ê Ê P Ì Ì Ê Ê P Ì Ì Ê Ê Ì Ì Ê Ê 0 0 A 0 V 00 0 00 min 1 0 00 min 1 pronto inser MotionControl scelta menu OP Upread OP Download scelta menu par utente menu parametri imp fissa scelta menu par utente menu parametri imp fissa Scelta impostazioni fisse P Ì Ì Ê Ê Ì Ì Ê Ê P Ì Ì Ê ...

Page 24: ...zionanento per il guasto presente Un guasto esistente viene tacitato con reset dopo aver eliminato la causa di guasto entro la segnalazione di funzionamento il tasto Reset deve essere parametrizzato in modo corrispondente ved paragr impostazione comandi attraverso OP1S Dal livello parametri si può ritornare direttamente alla visualizzazione di funzionamento premendo contemporaneamente P e diminuis...

Page 25: ...tre il riferimento da variare deve essere parametrizzato come valore di segnalazione nella 3 a riga della visualizzazione di funzionamento Tasto Funzione On Off1 EIN AUS1 Motopotenziometro riferimento aumenta diminuisci attivo solo in visual funzionam 0 a 9 o Impostazione riferimento mediante riferimento fisso attiva solo in visualizz funzionamento per immissione numerica quindi confermare con P I...

Page 26: ... Ì MotionControl canc dati cambio slave config slave configurazione indirizzo 00 Esempio per attivazion della funzione config slave Dopo aver inserito un indirizzo diverso per ogni slave con aumenta oppure per mezzo della tastiera numerica ed aver confermato con P avviene la configurazione cioè i parametri interfaccia vengono impostati ai valori standard paragrafo avviamento Inoltre viene scritto ...

Page 27: ...nta viene selezionata la funzione cambio di slave che viene attivata con P Ora viene chiesto all utente di immettere un indirizzo di slave Ê Ê P Ì Ì MotionControl Download can dati cambio slave cambio slave indirizzo 00 Esempio di attivazione della funzione cambio di slave Inserito un indirizzo di slave con aumenta opp diminuisci o per mezzo della tastiera numerica e conferma con P avviene il camb...

Page 28: ...ggio da 25 C a 70 C Temperatura trasporto 25 C bis 70 C Classe ambientale umidità sollecitazione sostanze nocive secondo DIN IEC 721 parte 3 3 04 90 3K3 3C3 Classe di protezione II secondo DIN VDE 0160 parte 1 05 82 IEC 536 1976 Grado di protezione parte frontale parte posteriore secondo DIN VDE 0470 parte 1 11 92 IP54 EN60529 IP21 Dimensioni L x A x P 74 x 174 x 26 mm Norme VDE 0160 E04 91 VDE 05...

Page 29: ...ection 14 4 9 Displaying and correcting parameters 15 4 10 Fault and alarm messages 20 4 11 Issuing commands via the OP1S 21 4 Bus operation 22 4 1 Configuring slaves 22 4 2 Change slave 23 5 Technical data 24 Note This operation manual of the OP1S is only valid for MASTERDRIVES units with the control boards CUVC and CUMC and for MASTERDRIVES Kompakt PLUS units The usage of the OP1S as spare part ...

Page 30: ......

Page 31: ...sing the USS protocol During communication the OP1S assumes the function of a master whereas the connected units function as slaves The OP1S can be operated at baud rates of 9 6 kBd and 19 2 kBd and is capable of communicating with up to 32 slaves addresses 0 to 31 It can therefore be used in a point to point link e g during initial parameterization or within a bus configuration The plain text dis...

Page 32: ... LCD 4 lines x 16 characters Sign key Reset key 0 to 9 number keys Jog 7 8 9 P Reset 0 4 5 6 1 2 3 O I Fault Run 9 pole SUB D connector on rear of unit LED green LED red Fig 1 1 View of the OP1S OP1S connection Pin Designation Meaning Range 3 RS485 P Data via RS485 interface 5 M5V Ground 6 P5V 5 V aux voltage supply 5 200 mA 8 RS485 N Data via RS485 interface 9 Reference potential Table 1 1 Connec...

Page 33: ... and adapter for installation in cabinet door Direct plugging into the units provided for it e g MASTERDRIVE Compact units or the Compact PLUS MASTERDRIVE rectifier unit Connection via cable S IE ME NS A S1 B X101 C X103 P USS Bus 7 3VO Jog 7 8 9 P Reset 0 4 5 6 1 2 3 O I Fault Run OP1S U S S v i a R S 4 8 5 5 4 3 2 1 9 8 7 6 5 4 3 2 1 9 8 7 6 OP1S side 9 pole SUB D socket Unit side 9 pole SUB D c...

Page 34: ...er active SIEMENS A S1 B X101 C X103 CM Rect Unit Inv USS bus on X100 OP1S mounted on rectifier unit SIEMENS A S1 B X101 C X103 Inv SIEMENS A S1 B X101 C X103 SIEMENS A S1 B X101 C X103 Inv Inv Fig 2 2 Example The OP1S during bus operation with Compact PLUS units NOTE During bus operation the Compact PLUS rectifier unit is only for mechanically restraining the OP1S and for connecting the bus to th...

Page 35: ...etting with the unit s own control panel a point to point link can be adopted with the OP1S without any further preparatory measures When a bus system is started up with the OP1S the slaves must first be configured individually The plugs of the bus cable must be removed for this purpose see section Bus operation During the run up phase the text Search slave is shown in the first line of the displa...

Page 36: ...P key is pressed the connected unit is reconfigured i e the interface parameters are set to the standard values Number of PKWs 127 Number of PZDs 2 or 4 Telegram failure time 0 ms If communication with the slave is still impossible the reasons may be as follows Defective cabling Bus operation with two or more slaves with the same bus address see section Bus operation The baud rate set in the slave...

Page 37: ...rization Toggle key For selecting menu levels and switching between parameter number parameter index and parameter value in the sequence indicated The current level is displayed by the position of the cursor on the LCD display the command comes into effect when the key is released For concluding a numerical input Reset Reset key For leaving menu levels If fault display active this is for acknowled...

Page 38: ...the operating display except for slave number 1st line on the far right can be specified by means of parameterization 1st line left in the example Output current 1st line right in the example DC link voltage 2nd line actual value in the example Actual speed only a visualization parameter 3rd line setpoint in the example Speed setpoint 4th line in the example Operating state In the operating displa...

Page 39: ...ines cannot be shown at the same time it is possible to scroll the display as required with the Lower and Raise keys Ê Ê Ì Ì Ê Ê Ì Ì Ê Ê Ì Ì Ê Ê Ì Ì MotionControl Menu selection OP Upread OP Download MotionControl Menu selection OP Upread OP Download MotionControl Menu selection OP Upread OP Download MotionControl OP Upread OP Download Delete data MotionControl OP Download Delete data Change slave...

Page 40: ...the Slave ID function is selected with Raise or Lower and activated with P As all the lines cannot be shown at the same time it is possible to scroll the display as required with the Lower and Raise keys In addition the slave number is shown at the top on the right hand side Ê Ê P Ì Ì Ê Ê Ì Ì Ê Ê Ì Ì Ê Ê Ì Ì MotionControl Change slave Config slave Slave ID MotionControl 00 Slave ID MASTERDRIVES MC...

Page 41: ...de Ê Ê P Ì Ì MotionControl Menu selection OP Upread OP Download MotionControl 00 Upread Pxxx Example Selecting and starting the Upread procedure With Reset the procedure can be interrupted at any time If the upread procedure has been completed in full the user is requested to enter an ID with a maximum of 12 characters for the stored parameter set This identification can for example consist of the...

Page 42: ...ise or Lower see section Slave ID The Download procedure is then started with P During download the OP1S displays the currently written parameters Ê Ê P Ì Ì Ê Ê P Ì Ì Download 1909199701 MASTERDRIVES MC PLUS Download 1909199701 MASTERDRIVES MC PLUS MotionControl 00 Download Pxxx Example Confirming the ID and starting the Download procedure With Reset the procedure can be stopped at any time If dow...

Page 43: ...e and activated with P Ê Ê P Ì Ì MotionControl OP Upread OP Download Delete data Delete data 1909199701 MASTERDRIVES MC PLUS Example Selection and activation of the Delete data function One of the parameter sets stored in the OP1S must now be selected with Lower or Raise displayed in the second line With P the selected ID is confirmed The slave ID can now be displayed with Lower or Raise see secti...

Page 44: ...menu level If Parameter menu is selected access is possible to all parameters via correspondingly structured sub menus If UpR fr access is selected direct access is gained to the parameter level 7x Ê Ê P Ì Ì Ê Ê Ì Ì Ê Ê Ì Ì MotionControl Menu selection OP Upread OP Download Menu selection User Param Param Menu FixedSet Menu selection Drive Setting Download UpR fr access r001 9 Drive status Ready E...

Page 45: ... parameter number with the numerical keypad Ê Ê Ì Ì Ê Ê Ì Ì Ê Ê Ì Ì r001 9 Drive status Ready r002 0 min 1 Actual speed r004 0 0 A Output Amps r006 0 V DC Bus Volts Example Correcting the parameter number by means of Raise If the parameter is found not to exist when the number is entered a message No PNU appears A non existent parameter number can be skipped by selecting Raise or Lower How the par...

Page 46: ...and selection text 1st line Parameter number parameter index parameter value 2nd line Parameter name 3rd line Index text 4th line Selection text P053 0006Hex Parameter Access 0000000000000110 ComBoard No Example Parameter without index with selection text binary value 1st line Parameter number hexadecimal parameter value 2nd line Parameter name 3rd line Parameter value binary 4th line Selection te...

Page 47: ...meter value and return to the parameter number does not take place until P is pressed The level selected in each case parameter number parameter index parameter value is marked with the cursor If an incorrect parameter value is entered the old value can be obtained by pressing Reset The Reset key can also be used to go one level lower Parameter value Reset Parameter index Reset Para No Parameters ...

Page 48: ... value Correction of parameter value Accept and return Ê Ê P Ì Ì Ê Ê 5 Ì Ì Ê Ê P Ì Ì P600 0 ms ContactorMsgTime P600 0ms ContactorMsgTime P600 5 ms ContactorMsgTime P600 5 ms ContactorMsgTime Selection of parameter index Correction of parameter index Ê Ê P Ì Ì Ê Ê Ì Ì Ê Ê P049 001 4 OP OperDisp 1st line left P049 001 4 OP OperDisp 1st line left P049 002 6 OP OperDisp 1st line right Selection of pa...

Page 49: ...ick parameterizing or if Fixed setting is selected In this case parameterization is carried out via various sub menus Example of how to proceed for a parameter reset 2x Ê Ê P Ì Ì Ê Ê P Ì Ì Ê Ê Ì Ì 0 0 A 0 V 00 0 00 min 1 0 00 min 1 Ready MotionControl Menu selection OP Upread OP Download Menu selection User Param Param Menu Fixed set Menu selection User Param Param Menu Fixed set Selection of fixe...

Page 50: ...hours are shown when a fault is waiting to be remedied After the cause of a fault has been removed the fault is acknowledged with Reset inside the operating display the Reset key must be appropriately parameterized See section Issuing commands via the OP1S By pressing P and Lower at the same time it is possible to skip back directly to the operating display from the parameter level When there is a...

Page 51: ...rconnected In addition the setpoint to be changed is to be parameterized as a displayed value in the 3rd line of the operating display Key Function ON OFF1 Motor potentiometer setpoint higher lower only effective within the operating display 0 to 9 or Setpoint specification by means of fixed setpoint only effective within the operating display If entered with numerical key confirm with P Reversing...

Page 52: ... Ê Ê P Ì Ì MotionControl Delete data Change slave Config Slave Configuration Address 00 Example of activating the Config slave function After a different slave address for each slave has been entered by means of the Raise key or with the numerical keypad and confirmed with P configuration is carried out i e the interface parameters are set to the standard value see section Run up In addition the s...

Page 53: ...the Change slave function is selected with the Lower Raise key and activated with P The user is then requested to enter a slave address Ê Ê P Ì Ì MotionControl Download Delete data Change slave Change slave Address 00 Example of activating the Change slave function After the slave address has been entered with Raise Lower and confirmed with P a change is made to the required slave and the display ...

Page 54: ...perature 25 C to 70 C Transport temperature 25 C to 70 C Environment class Humidity Pollution resistance Acc to DIN IEC 721 Part 3 3 04 90 3K3 3C3 Protection class II acc to DIN VDE 0160 Part 1 05 82 IEC 536 1976 Degree of protection Front Rear Acc to DIN VDE 0470 Part 1 11 92 IP54 EN60529 IP21 Dimensions W x H x D 74 x 174 x 26 mm Standards VDE 0160 E04 91 VDE 0558 Part 1 07 87 UL CSA Battery lif...

Page 55: ......

Page 56: ... 6R A5E00387560 L edizione AA è composta dai seguenti capitoli Capitolo Variazione Data edizione 1 Generalità prima edizione 02 98 2 Allacciamento avviamento prima edizione 02 98 3 Comando prima edizione 02 98 4 Funzionamento bus prima edizione 02 98 5 Dati tecnici prima edizione 02 98 Version AA consists of the following chapters Chapter Changes Version date 1 General First edition 02 98 2 Connec...