Siemens OP121 Installation Instructions Download Page 3

A6V10281367_d_en_--

3

FLASHING AT START-UP

Only during the first 180 seconds:

Flash
Color

Condition

Flash  Interval
(Seconds)

Green

Configuration
- Open area:

double flash

- Air duct:

triple flash

10

Yellow

Fault

5

Red

Alarm

2.5

No
Flashes

Low voltage

DETECTOR CONFIGURATION

Two programmed parameter sets can be changed with
the magnetic switch:

 

Standard (open area protection)

 

Duct (In Duct or Duct Housing application)

In Duct application with OH121 and OP121.
Duct Housing application only with OP121.

NOTE
Detectors  with  product  version  <17  only  have  one
parameter  set.  When  using  detectors in  air  duct
applications set to the parameter to “Duct”.

Magnetic Switch Logic

 

Alarm detection is always active, whether the switch
is applied or not.

 

Magnet shall be applied to the device after startup is
finished which is indicated by the blinking LED.

In case of fault or alarm the magnetic switch is turned
off.

FLASHING DURING CONFIGURATION

Magnet
applied

(seconds)

Behavior /
Operation

LED Indication

Color / time (seconds), flashing

<2.75

2.75 to 10

Normal

Red / 2.5, single flash

2.75 to 10
Magnet
released

Alarm

Red / 2.5, single flash

>10

Normal

30 seconds per configuration
(Starting with current setting)

- Open area: Green / 10, double flash

- Air duct: Green / 10, triple flash

>10

Magnet
released

Current
settings
confirmed
Normal

30

seconds per applied setting

- Open area:  Green / 10, double flash

- Air duct:

 

Green / 10, triple flash

TESTING AND MAINTENANCE

To  assure  proper  operation  of  the detector  and  control
panel, it is required that both the Sensitivity test and the
Functional  test  be  conducted  using  the  procedures
outlined below.

SENSITIVITY TEST

The  OP121/OH121  monitors  its  smoke  sensitivity
automatically  and  requires  no  test equipment.  A  green
flash  of  the  detector  LED  about  every  10 seconds
indicates  that  the  smoke  sensitivity  is  within  its  listed
limits.

FUNCTIONAL TEST

To  test  the  detector  and  control  panel  for  functional
operation  follow  the  instructions  on  the  gas  canister
label.

Perform  a functional  (Go,  No-Go) test  by  activating  the
detector using the following test gases:

 

Smoke Sabre, P/N SMOKESABRE-01-001

 

Smoke Centurion (M8), P/N M8-001-024

 

Solo A5 P/N SOLOA5 001

 

Solo A10, P/N SOLO A10 / A10s

 

Testifire 1001 / 2001, P/N TS3-001

 

HSI PurCheck, P/N HO-30S

 

HSI SmokeCheck™, P/N HO-25S

This test is simply used to ensure that smoke can enter
the sensing chamber and alarm the control panel when
the  detector  reaches  the  programmed  obscuration
(concentration) level.
Detector  and  control  panel  functionality  can  also  be
tested using  the  TM121  test  magnet  as  shown  in
Figure 4 and Figure 6. Place the magnet in the specific
area  at  the  bottom  of  the  detector  that  is shown  in
Figure 5  and  Figure 7  for  at  least  2.5 seconds  with  the
colored side towards the centered LED. The detector will
send an alarm to the panel.

Summary of Contents for OP121

Page 1: ... with STI Mechanical Protection Guard Model STI 9604 see www sti usa com for details Electrical Voltage 16 27 VDC Ripple 3 V peak to peak Supervisory Current 100 μA max Alarm Current 30 50 mA Start up Time 30 seconds max DO NOT install this detection device until all construction is completed DO NOT store this detection device where it can be contaminated by dirt dust or humidity DETECTOR PLACEMEN...

Page 2: ... The detector is marked DO NOT PAINT This is intended to prohibit painting during routine maintenance of the occupancy which can affect proper operation of the detector LED INDICATOR OPERATION The OP121 OH121 contains an LED indicator capable of flashing either one of three distinct colors green yellow or red The microprocessor based detector monitors the following Smoke in its sensing chamber Smo...

Page 3: ...mal 30 seconds per applied setting Open area Green 10 double flash Air duct Green 10 triple flash TESTING AND MAINTENANCE To assure proper operation of the detector and control panel it is required that both the Sensitivity test and the Functional test be conducted using the procedures outlined below SENSITIVITY TEST The OP121 OH121 monitors its smoke sensitivity automatically and requires no test...

Page 4: ...36866 FDBZ492 PR A6V10330327 FCC Statement WARNING Installation and usage of equipment not in accordance with instructions manual may result in Radiation of radio frequency energy Interference to radio communications Install and use equipment in accordance with installation instructions manual Read the following information AVERTISSEMENT L installation et l utilisation d équipement non conforme au...

Reviews: